Using an AGS Module: Operation
Page 98
©
2017 Sensata Technologies
To manually start the generator and have it automatically stop:
From the AGS Home screen (to access, refer to Section 8.1.1.1):
1. Press the CTRL button.
2. Turn the SELECT knob to the
03 Gen Control
menu.
3. Press the SELECT knob. The
Set Gen Control
menu displays with an arrow to the right of the
current setting.
4. Turn and press the SELECT knob to select the
ON
setting. The selection arrow appears to the
right of the screen. The generator should start at this time.
After the generator is running, rotate the SELECT knob to
AUTO
(under the
CTRL: 03 Gen Control
menu), and then press the SELECT knob to select the
AUTO
setting.
Note:
When the generator is manually started, and then changed to autostop, the SETUP: 04A Gen
Run DC Volts stop settings are used to determine when the generator autostops. If the SETUP: 04A
Gen Run VDC is set to OFF, the Start/Stop Delay and Stop Volts values that were entered prior to
selecting OFF will still be used to autostop the generator.
If the generator does not start or stop as expected, refer to Section 8.3.
To manually start the generator:
From the AGS Home screen (to access, refer to Section 8.1.1.1):
1. Press the CTRL button.
2. Turn the SELECT knob to the
03 Gen Control
menu.
3. Press the SELECT knob. The
Set Gen Control
menu displays with an arrow to the right of the
current setting.
4. Turn and press the SELECT knob to select the
ON
setting. The selection arrow appears to the
right of the screen. The generator should start at this time.
If the generator does not start as expected, refer to
Section 8.3.
To manually stop the generator:
From the AGS Home screen (to access, refer to Section 8.1.1.1):
1. Press the CTRL button.
2. Turn the SELECT knob to the
03 Gen Control
menu.
3. Press the SELECT knob. The
Set Gen Control
menu displays with an arrow to the right of the
current setting.
4. Turn and press the SELECT knob to select the
OFF
setting. The selection arrow appears to the
right of the screen. The generator should stop at this time.
If the generator does not stop as expected, refer to Section 8.3.
8.2.4
Starting and Stopping the Generator
The generator can be manually started/stopped, as well as autostarted/autostopped using the
available settings from your ME-ARTR.
To autostart/autostop the generator:
In order for the generator to autostart/autostop, one or more of the following autostart/autostop
conditions must be pre-set (see Section 8.1):
Autostart Conditions
• 04A Gen Run DC Volts (pp. 82-83)
• 04B Gen Run Time (p. 84)
• 04C Gen Run AC Amps (pp. 84-85)
• 04D Gen Run SOC (pp. 85-86)
• 04E Gen Run Temp (pp. 86-87)
• 04H Gen Exercise (pp. 90-91)
• 04J Gen 100% SOC (pp. 92-93)
Autostop Conditions
• 04A Gen Run DC Volts (pp. 82-83)
• 04B Gen Run Time (p.
84)
• 04C Gen Run AC Amps (pp. 84-85)
• 04D Gen Run SOC (pp. 85-86)
• 04E Gen Run Temp (pp. 86-87)
• 04F Max Gen Run Time (p. 88)
• 04G Gen Quiet Time (pp. 88-89)
• 04H Gen Exercise (pp. 90-91)