Using an AGS Module: Operation
Page 100
©
2017 Sensata Technologies
Auto Gen Start
Gen Ready 0.0Hrs
28.8VDC TS Open
P6 AGS Home
Inverting
Gen Ready
24.0VDC 12.0ADC
ALL System Home
System Home Screen – to
access, press and hold
METER button for 3 sec
PORT
SETUP
04A Gen Run DC Volts
Start=23.0V/120secs
Stop =28.8V/120secs
P6 View AGS SETUP
Press PORT button until port# to
which AGS is connected appears
(i.e., AGS Home Screen)
Press SETUP button to
access AGS menus
Note:
The AGS-N SETUP menus are accessed via the System Home screen and PORT button; or, by
pressing the SETUP button and rotating to the 04 AGS Setup menu, and then pressing the SELECT
knob. Refer to the procedures below to access these menu items via the AGS Home screen.
R
SETUP
Set Gen Run DC Volts
Start Volts = 23.0V
Stop Volts = 28.8V
P6 edit AGS SETUP
Set VDC Delay Times
Start Delay=120secs
Stop Delay =120secs
P6 edit AGS SETUP
04A Gen Run DC Volts
Start=23.0V/120secs
Stop =28.8V/120secs
P6 View AGS SETUP
04B Gen Run Time
Start Daily=11:30AM
Stop Daily =10:00PM
P6 View AGS SETUP
Set Gen Run Time
Start Daily=11:30AM
Stop Daily =10:00PM
P6 edit AGS SETUP
04C Gen Run AC Amps
Start = 25A /120secs
Stop = 4A /120secs
P6 View AGS SETUP
P
P
Start=OFF, 18.0-31.8
Stop
=
18.2-32.0,
Float
R
P
OFF, Start/Stop
Time=12:00AM-11:45PM
R
Set Gen Run AC Amps
Start AC Amps = 25A
Stop AC Amps = 4A
P6 edit AGS SETUP
P
Set Amps Delay Time
Start Delay=120secs
Stop Delay =120secs
P6 edit AGS SETUP
P
Start Amps= OFF, 5-60
Stop Amps= 4-59
0-127secs, 1-127mins
Delay= 0-127secs,
1-127mins
Set Gen Run SOC
Start SOC = 50%
Stop SOC = 90%
P6 edit AGS SETUP
04D Gen Run SOC
Start SOC = 50%
Stop SOC = 90%
P6 View AGS SETUP
04E Gen Run Temp
Start Temp= 65F
Run Time = 2.0Hrs
P6 View AGS SETUP
Set Gen Run Temp
Start Temp= 65F
Run Time = 2.0Hrs
P6 edit AGS SETUP
04F Max Gen Run Time
when Autostarted
= 12.0 Hours
P6 View AGS SETUP
P
R
P
R
Set Max Gen Run Time
when Autostarted
= 12.0 Hours
P6 edit AGS SETUP
P
OFF, 0.1-25.5Hrs
Start
=
OFF, ExtInput, 65F-95F
Run
=
0.5-25.5 Hrs*
R
Start = OFF, 20-99%
Stop
=
21-100%
x2
x2
* Shows if a start temp
selected
Note:
If
ExtInput
is
selected, once you press
SELECT the following
screen appears.
04E Gen Run Temp
Start Temp=ExtInput
P6 View AGS SETUP
Note:
04C applies only
to MS-PAE, MS-PE, and
MSH Series inverters.
Figure 8-3, AGS SETUP Menu Maps (Section 1)