Setup
©
2017 Sensata Technologies
Page 21
Figure 3-7, Current Flow – Standby Mode
Figure 3-8, Current Flow – Load Support Mode
Figure 3-6, Current Flow – Inverter Mode
INVERT MODE
Current from the battery is used by the inverter
to power the inverter’s AC loads.
Example below:
x
Current to inverter input (AC Input)
= 0 Amps AC
x
Current from battery (Inv/Chg Amps)
= -10 Amps AC
x
Current to power the AC loads (AC Load)
= 10 Amps AC
02B AC Amps:
AC Load = 10 AAC
AC Input = 0 AAC
P1 Read AC METER
02C Inv/Chg Amps
(In/Out of Battery)
-10 Amps AC
P1 Read AC METER
MAGNUM
INVERTER
AC Input =
0 Amps AC
A
AC Load =
10 Amps AC
Inv/Chg Amps=
-10 Amps AC
A
Inverter
Amp meters
=
A
A
AC CURRENT
(GRID/GEN)
DC CURRENT
(BATTERY)
INVERTER
AC LOADS
-120ADC
.
FROM
BATT
0AAC
FROM
GRID
10AAC
TO
LOADS
STANDBY MODE
Current from the grid/generator to the inverter’s
AC input is used to power the inverter’s AC loads
and to charge the battery.
Example below:
x
Current to inverter input (AC Input)
= 20 Amps AC
x
Current to power the AC loads (AC Load)
= 10 Amps AC
x
Current to charge battery (Inv/Chg Amps)
= 10 Amps AC
MAGNUM
INVERTER
AC Input =
20 Amps AC
A
AC Load =
10 Amps AC
Inv/Chg Amps=
10 Amps AC
A
Inverter
Amp meters
=
A
A
AC CURRENT
(GRID/GEN)
DC CURRENT
(BATTERY)
INVERTER
AC LOADS
120ADC
TO
BATT
-20AAC
.
FROM
GRID
10AAC
.
TO
LOADS
.
02B AC Amps:
AC Load = 10 AAC
AC Input = 20 AAC
P1 Read AC METER
02C Inv/Chg Amps
(In/Out of Battery)
10 Amps AC
P1 Read AC METER
LOAD SUPPORT MODE
(MSH Series Only)
The MSH Series uses current from the battery to
assist in powering the
inverter’s AC loads
and to
reduce the current from the grid/generator.
Example below:
x
Current to inverter input (AC Input)
= 10 Amps AC
x
Current to power the AC loads (AC Load)
= 20 Amps AC
x
Current from battery (Inv/Chg Amps)
= -10 Amps AC
MSH SERIES
INVERTER
AC Input =
10 Amps AC
A
AC Load =
20 Amps AC
Inv/Chg Amps=
-10 Amps AC
A
Inverter
Amp meters
=
A
A
AC CURRENT
(GRID/GEN)
DC CURRENT
(BATTERY)
INVERTER
AC LOADS
-120ADC
FROM
BATT
-10AAC
.
FROM
GRID
20AAC
.
TO
LOADS
.
02B AC Amps:
AC Load = 20 AAC
AC Input = 10 AAC
P1 Read AC METER
02C Inv/Chg Amps
(In/Out of Battery)
-10 Amps AC
P1 Read AC METER