Using an AGS Module: Operation
©
2017 Sensata Technologies
Page 97
METER: 04F Since 100% Days Menu
This read-only menu displays the number of days since the battery was at 100% SOC, and is
calculated in the ME-AGS-N. It is used by the SETUP button’s
04J Gen 100% SOC Start
feature
to determine when to command the ME-AGS-N to autostart the generator.
Info:
This display resets once the battery SOC reaches 100%, power to the AGS is lost,
or the data communications from the BMK is lost.
Info:
The
METER: 04F Since 100% Days
menu uses information from the
METER: 05A
BMK SOC
menu to determine the last time the battery SOC was 100%.
Info:
For the
METER: 04F Since 100% Days
to increment, the
METER: 05A BMK
SOC
display must not display
100%
(or
No Comm
), the optional ME-AGS-N must be
connected and enabled (
CTRL: 03 Gen Control = AUTO
) and the
SETUP: 04J Gen 100%
SOC
must also be enabled (not set to
OFF
).
Info:
The
METER: 04F Since 100% Days
menu, which is calculated in the ME-AGS-N,
is similar to the
METER: 05I Days Since 100%
menu (which is calculated in the router).
If an AGS is installed at a later date (or the router is reconnected), the two menus will
not be coordinated with each other. However, they will automatically synchronize once
the BMK’s
METER: 05A BMK SOC
menu reaches 100% SOC, or they can be manually
synchronized by momentarily removing the network cable from the BMK.
METER: 04G Gen Hour Meter Menu
This menu displays how many hours the generator has run since this “hour meter” was last reset.
This menu is helpful if you would like to keep track of how long the generator has run from a
speci
fi
c point; for example, after the generator has been serviced.
Note:
The Gen Hour Meter menu’s timer starts when the gen run sense voltage (10-40 volts DC)
from the generator to Pin 2 (+) and Pin 4 (-) is present on the AGS module.
Info:
The
Gen Hour Meter
menu’s timer can register elapsed time up to 65,000 hours,
and can be reset to “
0 Hours
” by pressing and holding the SELECT button for ~3 secs.
Info:
The hour meter will not count if the Gen Type DIP switch inside the AGS module is
set to “
2-Wire-Standby
” because this setting does not require the gen run sense voltage
from the generator to the AGS.
Info:
The
CTRL: 03 Gen Control
setting has no effect on the whether the hour meter is
active or not.
Info:
The gen hours shown in this menu are calculated in the AGS. They do not reset
if the inverter or router loses power, but they do reset if the AGS module loses power.
METER: 04E Since Run Days Menu
This read-only menu displays the number of days since the generator has last run. The Since Run
Days timer begins once the
CTRL: 03 Gen Control
menu is set to
AUTO
, and then counts by one
day for every 24-hour period that the generator does not start. The Since Run Days timer resets
any time the gen run sense signal is present on Terminal 2 of the AGS, which could be either
by autostarting the generator (including from a previous exercise run), or manually starting the
generator (using the ME-ARTR).
Info:
When the DIP switch inside the AGS is set to “2-Wire Standby Mode”, which does
not require the gen run sense signal to be present on Terminal 2 of the AGS, the Since
Run Days timer will not be reset to zero.
Info:
If a MSH4024RE (dual AC input inverter) is used, the Since Run Days timer also
resets any time voltage is present on the AC2 (Gen) input.