Setup
Page 42
©
2017 Sensata Technologies
◊
Set
Final Charge Stage = Silent
–
If Silent mode is selected as the
fi
nal charge stage,
the charger stops charging once it transitions to ‘
Silent
’. Normally, the charger enters Silent
mode after the absorption charge mode has
fi
nished, and after entering the Silent mode, the
battery voltage is continuously monitored. If the batteries fall to the
Set DC Volts to Rebulk
value, the charger restarts the Bulk Charge mode and then transitions to Absorption Charge
mode. After the Absorption Charge mode, the charger again transitions to Silent mode.
This silent to Rebulk to Absorb and back to Silent cycle continues as long as it is required.
See Figure 3-16.
□
Set DC Volts to ReBulk
– When
Silent
mode is selected, you must also set the DC
voltage set-point where the charger restarts the Bulk Charge mode. This setting should
be at the lowest DC volts you want the batteries to fall before starting a new bulk charge.
Typically, the lowest DC volts the batteries are allowed to fall is 12.0 to 12.2 VDC (12-volt
systems), 24.0 to 24.4 VDC (24-volt systems), and 48.0 to 48.8 VDC (48-volt systems),
respectively.
Default setting:
DC Volts to ReBulk = 12.0 VDC(12v), 24.0 VDC(24v), 48.0 VDC (48v)
Ranges:
12.0-16.0 VDC (12v), 24.0-32.0 VDC (24v), 48.0-64.0 VDC (48v)
Why should I use the Silent Stage?
Silent mode is typically used when an alternate charge
source is available and able to fully charge or
fi
nish the charge cycle after the Absorb stage. A
major difference between Multi-Stage mode and Silent mode is that the Silent mode returns to
Bulk mode instead of Float mode. In Silent mode you can also adjust the rebulk set-point in order
to allow the alternate charge source to provide more of the battery charging.
• 03G Always Start Charge in Bulk:
When this setting is enabled, the charger automatically
goes into the Bulk charge mode each time AC is connected to the inverter’s AC input.
Default setting:
Disabled
Range:
Enabled, Disabled
Why should I enable the Always Start Charge in Bulk setting?
Normally, when an AC
source is connected to the inverter’s AC input, the inverter makes a decision on which charge
mode to enter based on the battery voltage level. If the battery voltage is at a high level (over
26.0 VDC for 24-volt models or 52.0 VDC for 48-volt models), the charge automatically goes into
the Float charge mode to keep from overcharging the batteries. Some battery types (i.e., Lithium)
normally rest at a high voltage level. With these battery types, the charger would always go into
fl
oat charge, which may not allow these battery types to be fully charged. Enabling the
Always
Start Charge in Bulk
setting will cause the charger to automatically go into the Bulk charge mode
and go through a full charge each time AC is connected to the inverter’s AC input.
3.3.4.1 Accessory
Setup
Like the previous SETUP menu items, the accessory SETUP menus are accessed through the
SETUP button and the accessory’s “Home” screen under the PORT button. However, the
AGS
Setup
,
BMK Setup
,
RC Setup
, or
PT Setup
menus only display if the related accessory is connected
and communicating with the router unless the
TECH: 08 Show all Menus
menu has been set to
“
YES
”. Refer to page 47 for more information on the
TECH 08
menu. Otherwise,
“No *** Present”
appears when accessing any menu that uses the speci
fi
c accessory.
Note:
*** refers to the accessory not present (i.e., “No AGS Present”, “ No BMK Present”, “No
Remote Present”, or “No PT Present”.).
SETUP: 04 AGS Setup
This menu is used to set up the functions related to the ME-AGS-N (Automatic Generator Start
– Network version). Refer to Section 8.0 “Using an AGS Module” for detailed information on the
available AGS menus using the router.
Info:
For installation information on the ME-AGS-N, refer to your AGS owner’s manual
(PN: 64-0039).