Table 3-3, Inverter/Charger Default Settings on ME-ARTR
Menu Items
Default Settings
Search Watts
5 Watts
LowBatCutOut
10 VDC (12v), 20 VDC (24v), 40 VDC (48v)
AC In – Time
Connect = 6:00AM, Disconnect = 6:00PM
AC In – Volts DC
Connect = 11.0V (12v), 22.0 (24v), 44.0 (48v)
Disconnect = 14.1V (12v), 28.2V (24v), 56.4V (48v)
AC In – SOC
Connect = 80%, Disconnect = 100%
Inv Always Power-Up
NO
Inv Threshold to Start Parallel
60%
AC Input Amps
30 Amps (AC1), 20 Amps (AC2)
*
Low VAC Dropout
80 VAC (AC1), 70 VAC (AC2)
*
, (Exports – 150 VAC)
Battery Type
Flooded
Absorb Done
Time = 2.0 Hrs, Amps = 20 ADC, SOC = 100%
Max Charge
Rate = 100%, Time = 12.0 Hrs
Final Charge Stage
Multi-Stage
Always Start Charge in Bulk
Disabled
*
AC2 settings available on MSH4024RE models only
.
TECH: 07 Ext Control
The
External Control
menu is read only. Sensata has an open protocol policy which allows third
party
fi
rmware companies to control certain functions of the inverter/charger. This menu displays
if any external device/software is controlling the router. It is designed to help support staff
determine if the inverter/charger is operating normally, or is being controlled by a third party.
•
NO
– Indicates no third party network device is controlling the router.
•
YES
– Indicates a third party network device is currently controlling one of the allowable
router functions (third party functions displayed as a number). This number can be used by
Tech Support to determine what code is controlling the router.
TECH: 08 Show all Menus
This menu enables you to have the router display all available screens (
YES
), or to just display
those screens that pertain to the devices and accessories currently active (
NO
).
Info:
You can lock this menu to “YES” by pressing and holding the SELECT button when
the
Show all Menus
menu displays in View mode. “YES” is locked on power-down, but
not after a factory default reset.
TECH: 09 Load New Firmware
This menu enables you to update the router’s
fi
rmware using a SD card. Refer to Section 7.0 for
more information, and to the ME-ARTR Firmware Update Instruction Sheet (PN: 64-0092)—at
www.SensataPower.com
—for detailed instructions on performing the update procedure.
TECH: 10 Load All Defaults
This menu restores factory defaults to all settings on the inverter/charger and to any settings on
accessories that are networked. To restore, press and hold the rotary SELECT knob for 5 seconds
(“
Resetting...
” displays after 5 seconds). Refer to Table 3-3 for router default values.
Info:
For information on the factory default settings for any networked accessory, refer
to the owner’s manual for that accessory.
Info:
If the PIN has been set and locked, it must be entered before the
Load System
Defaults
menu can be used.