Operation
Page 58
©
2017 Sensata Technologies
FAULT
PWR
CHG
INV
Off
Settings/Info...
Off
appears on the LCD. All LEDs are off.
Figure 5-7, Off Mode
• Off
– This message tells you that there is no AC available on the inverter’s AC output. The
inverter function is OFF and there is no utility or generator AC power sensed on its input.
Figure 5-8, Searching Mode
Searching
appears on the LCD. The PWR (green)
LED is on solid and the INV (green) LED
fl
ashes. The
FAULT (red) and CHG (green) LEDs are off.
• Searching
(Search)
– The inverter is in Search mode—the AC loads on the inverter output
are less than the SETUP button’s
02A Search Watts
setting. The Search mode function reduces
the inverter draw from the battery, and may be turned off at any time for full inverter output.
FAULT
PWR
CHG
INV
Searching
Settings/Info...
FAULT
PWR
CHG
INV
Unknown Mode ##
Settings/Info...
Unknown Mode ##
appears on the LCD. The PWR
(green) LED is on solid and the INV (green) LED
fl
ashes. The FAULT (red) and CHG (green) LEDs are
off.
Figure 5-9, Unknown Mode ##
• Unknown Mode ## (Mode ##)
– This status message displays when the inverter/charger
has sent a fault code that cannot be determined by the router.
Remedy:
Call the Technical Support department at Sensata (425-353-8833) for
assistance in determining and understanding the actual fault status.
5.3.2
Charger Mode Status Messages
When AC power (utility or generator) is connected to the inverter/charger it monitors the AC input
for acceptable voltage. Once AC input is accepted, the AC transfer relay (within inverter) closes
and Charge mode begins. View the top line of the LCD display and the corresponding message in
this section to identify and understand the particular Charge mode that displays.
Info:
The AC input becomes acceptable once a minimum 10-second delay passes, the
voltage is greater than the SETUP button’s
03B Low VAC Dropout
setting, and there is
no
CTRL:
AC In Control
menu setting that is actively preventing the AC from connecting.
Inverter Standby
appears on the LCD. The INV
(green) LED is on solid. All other LEDs are off.
FAULT
PWR
CHG
INV
Inverter Standby
Settings/Info...
• Inverter
Standby
(Inv
Stby)
–
The inverter is on, but not actively providing power. However,
it is monitoring the power requirement of the parallel system to determine when to activate and
provide power to assist the master inverter.
Figure 5-6, Inverter Standby Mode
Содержание ME-ARTR