Using an AGS Module: Setup
Page 88
©
2017 Sensata Technologies
SETUP: 04F Max Gen Run Time when Autostarted Menu
This menu is used to set the maximum time the generator runs if autostarted.
• Max Gen Run Time when Autostarted
– Sets the maximum amount of time you want the
generator to run once it has been autostarted.
Default setting:
Max Gen Run Time when Autostarted = 12.0 Hrs
Range:
OFF, 0.1-25.5 Hrs (0.1 hr increments)
Why use Max Gen Run Time?
This setting ensures the generator does not run longer than
desired after an autostart. Designating a max run time ensures the generator stops if the autostop
setting cannot be satis
fi
ed.
Example:
If the fuel capacity of your generator is 5 hours, set the
Max
Gen Run Time
setting to 4.5 hours to ensure the generator does not run out of fuel.
Info:
When the generator autostarts, it stops when the autostop parameter for that
particular setting has been satis
fi
ed. For example, if the generator starts due to the
04A Gen Run DC Volts
menu’s autostart setting, it stops when the
Stop Volts
autostop
setting is satis
fi
ed; unless the
Max Gen Run Time
setting has been reached. The
Max
Gen Run Time
setting overrides any autostop setting and causes the fault LED to come
on and displays the
Fault MaxRn
status. If this happens, you may have to increase the
Max Gen Run Time
setting or adjust the autostop setting to
fi
nish sooner. If multiple
autostart settings are set and a
Fault MaxRn
status occurs, refer to the METER button’s
04A AGS Status
menu to identify which condition autostarted the generator. This way
you know which auto condition is running longer than the
Max Gen Run Time
setting.
Info:
The
Max Gen Run Time
menu uses the METER button’s
04C Gen Run Time
display
to determine the generator’s run time.
Info:
If the generator is stopped due to the
Max Gen Run Time
parameter being met,
the status becomes
Fault MaxRn,
and does not autostart again until you clear the fault
by selecting
OFF
under the
CTRL:03 Gen Control
menu.
SETUP: 04G Gen Quiet Time Menu
This menu is used to enable the
Quiet Time
feature and to set the period of time each day
in which the generator is not allowed to automatically run. The generator is prevented from
autostarting during the Quiet Time period. Also, if any autostart parameter in the
04 AGS Setup
menus has been met and the generator is running when the Quiet Time start setting is reached,
the generator turns off. The generator does not try to autostart until the Quiet Time stop setting
has been reached and an autostart condition is once again satis
fi
ed.
Info:
The ME-ARTR contains a real time clock that must be set for proper operation of
the
SETUP: 04G Gen Quiet Time
menu feature.
• Set Gen Quiet Time (Begin Quiet)
– Set the time you want Quiet Time to begin.
Default setting:
Begin Quiet = OFF
Range:
OFF,
12:00AM-11:45PM (15 minute increments)
• Set Gen Quiet Time (End Quiet)
– Set the time you want Quiet Time to end.
Default setting:
End Quiet = 10:00AM
Range:
12:00AM-11:45PM (15 minute increments)
• Set
Time to Topoff Battery before Quiet Time
–
This menu sets the time period the
generator autostarts and runs before Quiet Time begins. The generator only starts on Quiet
Time
topoff if the battery voltage is within 0.3 volts
¹
or less of reaching the
04A Gen Run DC
Volts
start parameter, or the battery’s SOC is within 4% or less of reaching the 04D Gen Run
SOC start parameter
²
.
Default setting:
Set Time to Topoff Battery before Quiet Time = OFF
Range:
OFF, 30-120 Minutes (30 minute increments)
Note¹:
This voltage is scaled depending on your battery system;
≤
0.3 for 12-volt systems,
≤
0.6
for 24-volt systems, and
≤
1.2 for 48-volt systems.
Note²:
Requires an optional Battery Monitor Kit (ME-BMK or ME-BMK-NS) installed and enabled.