Setup
Page 20
©
2017 Sensata Technologies
MSH models only:
• 02H
Input Volts AC1:
This menu displays the RMS value of the AC voltage at the inverter’s
AC1 and NEUTRAL input terminals.
MSH-RE models only:
• 02I Input Volts AC2:
This menu displays the RMS value of the AC voltage at the inverter’s
AC2 and NEUTRAL input terminals.
Info:
The
02I Input Volts AC2
menu only displays if the router is connected to a dual
source inverter/charger that has an AC1 and AC2 input, such as the MSH4024RE.
Info:
If the
02I Input Volts AC2
menu displays voltage (~ 50v), but the generator
is off or nothing is connected to the AC2 input, the AC2 neutral-to-ground bond
connection is not correct or not connected.
METER: 03 Timers
• 03A
Charge Time:
This meter displays the total time the charger is holding the batteries at
a high voltage level. The timer counts while in Bulk, Absorption, or Equalization charge stages
(or in the Constant Current and Constant Voltage charge stages if
CC/CV
is selected under the
SETUP/03C Battery Type
menu). The meter does not accumulate time when in Float, Charger
Standby, Full, or Silent mode. The charge timer resets whenever the charge status goes to
“Charging” (AC is connected to the inverter/charger), or the charger initiates another Bulk,
EQ, or Constant Current charge cycle.
Info:
The
03A Charge Time
value displayed is used by the Max Charge Time safety
feature to determine when to display “
Max Charge Time
” and blink CHG LED indicator.
Info:
The Max Charge Time safety feature is set and enabled based on the battery
type that is selected under the
SETUP/03C Battery Type
menu:
a) If the battery type is ‘
CC/CV
’ – the
Set Max CC/CV Charge Time
setting is available
to set after the
CV Chg Done Time
(or
Amps
) is selected under the
SETUP/03C Battery
Type: CC/CV
menu.
b) If the battery type is not ‘
CC/CV
’ – the
SETUP/03E Max Charge: Time
menu is
available to set the maximum charge time.
• 03B Days Since:
◊
Absorb/CV Done
– This menu displays the number of days since the Absorption charge
mode was completed (i.e.,
Absorb Done – Time, Amps, or SOC
). This menu resets to zero
once an Absorb Done is completed as per the
SETUP: 03D Absorb Done
setting.
Info:
The
03B Days Since: Absorb/CV Done
timer resets to zero once an Absorb Done
is completed as per the
SETUP: 03D Absorb Done
setting; or, the Absorption Charge
mode is
fi
nished prematurely by starting another charge mode—such as enabling a
Start Float charge (using
CTRL: 02 Charger Control/Start Float
).
◊
EQ Chg Started
– This menu displays the number of days since the EQ charge mode has
been enabled. This menu resets to zero once equalization has started. The
SETUP: 01I Days
to remind when to EQ
menu uses the time shown in this menu to determine when to indicate
it is time to perform an equalization charge to the batteries.
METER: 04 AGS Meters
Refer to Section 8.2.3.1 for information on all AGS menus available from the METER button.
METER: 05 BMK Meters
Refer to Section 9.2.2
for information on all BMK menus available from the METER button.
METER: 06 ACLD Meters
Refer to Section 11.2.1
for information on all ACLD menus available from the METER button.
METER: 07 PT Meters
Refer to Section 12.2.2.1
for information on all PT menus available from the METER button.