Using an AGS Module: Operation
Page 104
©
2017 Sensata Technologies
Status
Description
Fault Temp
(FaltTemp or FTmp)
The generator failed to start in Start Temp mode.
Fault Test
(FaltTest or FTst)
The generator failed to start in Test mode.
Fault Time Daily
(Falt TOD or FTOD)
The generator failed to start in Start Time mode.
Fault Topoff
(Falt Top or FTop)
The generator failed to start in Start Topoff mode.
Fault VDC
(Falt VDC or FVDC)
The generator failed to start in Start Volts DC mode.
Fault 100% SOC
(Falt100% or F100)
The generator failed to start in 100% SOC mode.
Table 8-5, AGS Router Fault Statuses (Cont.)
AGS SETUP Menus
Default Settings
04A Gen Run Volts DC
Start Volts = 11.5 VDC (12v), 23.0 VDC (24v), 46.0 VDC (48v)
Start Delay = 120 secs
Stop Volts = 14.4 VDC (12v), 28.8 VDC (24v), 57.6 VDC (48v)
Stop Delay = 120 secs
04B Gen Run Time
OFF
04C Gen Run AC
Amps*
OFF
04D Gen Run SOC
OFF
04E Gen Run Temp
OFF
04F Max Gen Run Time
12.0 Hrs
04G Gen Quiet Time
OFF
04H Gen Exercise
OFF
04I Gen No-Load Time
Warm-up = 60 secs
Cooldown = 60 secs
04J Gen 100% SOC
OFF
*MS-PAE, MS-PE and MSH Series models only
Table 8-6, AGS Default Settings on ME-ARTR
8.2.6.4
AGS General Notes
If a fault condition occurs, select the
OFF
setting from the
03 Gen Control
menu. If the problem
persists, refer to Section 8.3 “ME-AGS-N Router Troubleshooting (with the ME-ARTR)”.
• When
the
03 Gen Control
setting on the ME-ARTR is in the
OFF
position, all generator autostart
functions are disabled and the AGS’s STATUS indicator will also be off.
• When AGS control is set to
AUTO
, and an autostart condition occurs, it attempts an automatic
generator start. This is done by closing its internal relays (based on the Gen Type selection)
to control the starter—much like a person does when manually starting the generator. The
starter is turned on for short periods of time and then turned off. If the AGS determines that
the engine has started while cranking (STATUS indicator lights solid green), the starter is
turned off after a short delay. If the engine does not start, another attempt is made to turn on
the starter after a long delay period. This is repeated until the generator starts or until all its
start attempts are reached, which causes the AGS to go into a fault condition (indicated by a