Using an AGS Module: Troubleshooting
©
2017 Sensata Technologies
Page 107
Info:
Beginning with Version 5.2 of the ME-AGS-N, the
Max Gen Run Time
setting can be
defeated. In some cases, it may be appropriate to set the
Max Gen Run Time
setting to
OFF
. However, this feature is mainly provided as a safety feature to ensure the generator
doesn’t run longer than the time it takes to reach the autostop conditions or to expend
the generator’s fuel capacity, whichever occurs
fi
rst—take this into consideration if this
setting is defeated.
•
Fault SOC
– The generator failed to autostart and run per the
04D Gen Run SOC
menu’s start
parameters.
•
Fault Temp
– The generator failed to autostart and run per the
04E Gen Run Temp
menu’s
start parameters.
•
Fault Test
– The generator failed to autostart and run after the red TEST button is pressed
on the AGS module.
Note:
The ME-ARTR does not provide a “test” selection, instead it can be set to manually turn
the generator on and off, which can be used to test the generator wiring to the AGS.
•
Fault Time
Daily
– The generator failed to autostart and run per the
04B Gen Run Time
menu’s start parameters.
• Fault
Topoff
– The generator failed to autostart and run per the
04G Gen Quiet Time
menu’s
Topoff
start parameters.
•
Fault VDC
– The generator failed to autostart and run per the
04A Gen Run Volts DC
menu’s
start parameters.
•
Fault 100% SOC
– The generator failed to autostart and run per the
04J Gen 100% SOC
menu’s start parameters.
Remedy:
One of the above fault messages may display on the router when:
a) The AGS attempts to start the generator four times, but the generator failed to start
and run per the speci
fi
c autostart parameters; or,
b) The generator started, but did not provide the correct gen run sense signal to the
AGS module. For either scenario, refer to your AGS owner’s manual to troubleshoot why
the generator does not start or run.
8.3.2.1
How to Clear AGS Faults
To clear the AGS fault,
go to the
CTRL: 03 Gen Control
menu and select
OFF
. Once the fault is
cleared, you should test the AGS/generator system by performing the AGS Functional Test—to
see if the fault returns.
Note:
After troubleshooting the reason for the AGS fault, and then clearing the fault, be sure to
re-enable the AGS to autostart. Go to the CTRL: 03 Gen Control menu and select AUTO. Refer to
Figure 8-2.