RS-485
Communication Features
345
7.3 LS INV 485/Modbus-RTU Communication
7.3.1 Setting Virtual Multi-function Input
Multi-function input can be controlled using a communication address (0h0385). Set codes
COM-70
–77 to the functions to operate, and then set the BIT relevant to the function to 1 at
0h0385 to operate it. Virtual multi-function operates independently from IN-65
–71 analog
multi-function inputs and cannot be set redundantly. Virtual multi-function input can be
monitored using COM-86 (Virt Dl Status). Before you configure the virtual multi-function
inputs, set the DRV code according to the command source.
Group Code Name
LCD Display Parameter Setting Setting range
Unit
COM
70
–
77
Communication
multi-function input x
Virtual DI x
(x: 1
–8)
0
None
0
–55
-
86
Communication
multi-function input
monitoring
Virt DI
Status
0000 0000
0000 0000
–
1111 1111
bit
Example:
When sending an Fx command by controlling virtual multi-function input in the
common area via Int485, set COM-
70 to ‘FX’ and set address 0h0385 to ‘0h0001’.
7.3.2 Saving Parameters Defined by Communication
If you turn off the inverter after setting the common area parameters or keypad parameters
via communication and operate the inverter, the changes are lost and the values changed
via communication revert to the previous setting values when you turn on the inverter.
Set CNF-
48 to ‘1 (Yes)’ to allow all the changes over communication to be saved, so that
the inverter retains all the existing values even after the power has been turned off.
Setting address 0h03E0 to ‘0’ and then setting it again to ‘1’ via communication allows the
existing parameter settings to be saved. However, setting address 0h03E0 to ‘1’ and then
setting it to ‘0’ does not carry out the same function.
Group Code
Name
LCD Display
Parameter Setting Setting range Unit
CNF
48
Save parameters
Parameter
Save
0
No
0
No
-
1
Yes
Содержание LSLV-H100 Series
Страница 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 35: ...Installing the Inverter 22 ...
Страница 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Страница 181: ...168 Learning Advanced Features PID Command Block ...
Страница 182: ...169 Learning Advanced Features ...
Страница 183: ...170 Learning Advanced Features PID Feedback Block ...
Страница 184: ...171 Learning Advanced Features PID Output Block ...
Страница 185: ...172 Learning Advanced Features PID Output Mode Block ...
Страница 198: ...185 Learning Advanced Features EPID1 Control block ...
Страница 199: ...186 Learning Advanced Features EPID2 Control block ...
Страница 220: ...207 Learning Advanced Features ...
Страница 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Страница 506: ...Table of Functions 493 ...
Страница 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Страница 549: ...Troubleshooting 536 ...
Страница 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 570: ...Technical Specification 557 110 185 kW 3 phase ...
Страница 601: ...588 ...
Страница 602: ...589 ...
Страница 603: ...590 ...