121
Learning Basic Features
4.13 V/F (Voltage/Frequency) Control
Configure the inverter’s output voltages, gradient levels, and output patterns to achieve a
target output frequency with V/F control. The amount of torque boost used during low
frequency operations can also be adjusted.
4.13.1 Linear V/F Pattern Operation
A linear V/F pattern configures the inverter to increase or decrease the output voltage at a
fixed rate for different operation frequencies based on V/F characteristics. A linear V/F
pattern is particularly useful when a constant torque load is applied.
Group
Code
Name
LCD Display
Parameter Setting Setting Range
Unit
IN
09
Control mode
Control Mode
0
V/F
0
–1
-
18
Base frequency Base Freq
60.00
30.00
–400.00 Hz
19
Start frequency Start Freq
0.50
0.01
–10.00
Hz
BAS
07
V/F pattern
V/F Pattern
0
Linear
0
–3
-
Linear V/F Pattern Setting Details
Code
Description
DRV-18 Base
Freq
Sets the base frequency.
A base frequency is the inverter’s output
frequency when running at its rated voltage. Refer to the motor’s rating
plate to set this parameter value.
DRV-19 Start
Freq
Sets the start frequency. A start frequency is a frequency at which the
inverter starts voltage output. The inverter does not produce output voltage
while the frequency reference is lower than the set frequency. However, if a
deceleration stop is made while operating above the start frequency, output
voltage will continue until the operation frequency reaches a full-stop (0 Hz).
Содержание LSLV-H100 Series
Страница 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 35: ...Installing the Inverter 22 ...
Страница 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Страница 181: ...168 Learning Advanced Features PID Command Block ...
Страница 182: ...169 Learning Advanced Features ...
Страница 183: ...170 Learning Advanced Features PID Feedback Block ...
Страница 184: ...171 Learning Advanced Features PID Output Block ...
Страница 185: ...172 Learning Advanced Features PID Output Mode Block ...
Страница 198: ...185 Learning Advanced Features EPID1 Control block ...
Страница 199: ...186 Learning Advanced Features EPID2 Control block ...
Страница 220: ...207 Learning Advanced Features ...
Страница 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Страница 506: ...Table of Functions 493 ...
Страница 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Страница 549: ...Troubleshooting 536 ...
Страница 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 570: ...Technical Specification 557 110 185 kW 3 phase ...
Страница 601: ...588 ...
Страница 602: ...589 ...
Страница 603: ...590 ...