Troubleshooting
530
Type
Cause
Remedy
The set value for electronic thermal
protection is too low.
Set an appropriate electronic thermal
level.
The inverter has been operated at
low speed for an extended duration.
Replace the motor with a model that
supplies extra power to the cooling fan.
Out Phase
Open
The magnetic contactor on the
output side has a connection fault.
Check the magnetic contactor on the
output side.
The output wiring is faulty.
Check the output wiring.
In Phase
Open
The magnetic contactor on the input
side has a connection fault.
Check the magnetic contactor on the
input side.
The input wiring is faulty.
Check the input wiring.
The DC link capacitor needs to be
replaced.
Replace the DC link capacitor. Contact
the retailer or the LS ELECTRIC
customer service center.
Inverter OLT
The load is greater than the rated
motor capacity.
Replace the motor and inverter with
models that have increased capacity.
The torque boost level is too high.
Reduce the torque boost level.
Over Heat
There is a problem with the cooling
system.
Determine if a foreign object is
obstructing the air inlet, outlet, or vent.
The inverter cooling fan has been
operated for an extended period.
Replace the cooling fan.
The ambient temperature is too high.
Keep the ambient temperature below
50
℃
.
Over
Current2
Output wiring is short-circuited.
Check the output wiring.
There is a fault with the electronic
semiconductor (IGBT).
Do not operate the inverter. Contact the
retailer or the LS ELECTRIC customer
service center.
NTC Open
The ambient temperature is too low.
Keep the ambient temperature above -
10
℃
.
There is a fault with the internal
temperature sensor.
Contact the retailer or the LS
ELECTRIC customer service center.
Fan Lock
/ In Fan
A foreign object is obstructing the
fan’s air vent.
Remove the foreign object from the air
inlet or outlet.
The cooling fan needs to be
replaced.
Replace the cooling fan.
Содержание LSLV-H100 Series
Страница 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 35: ...Installing the Inverter 22 ...
Страница 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Страница 181: ...168 Learning Advanced Features PID Command Block ...
Страница 182: ...169 Learning Advanced Features ...
Страница 183: ...170 Learning Advanced Features PID Feedback Block ...
Страница 184: ...171 Learning Advanced Features PID Output Block ...
Страница 185: ...172 Learning Advanced Features PID Output Mode Block ...
Страница 198: ...185 Learning Advanced Features EPID1 Control block ...
Страница 199: ...186 Learning Advanced Features EPID2 Control block ...
Страница 220: ...207 Learning Advanced Features ...
Страница 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Страница 506: ...Table of Functions 493 ...
Страница 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Страница 549: ...Troubleshooting 536 ...
Страница 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 570: ...Technical Specification 557 110 185 kW 3 phase ...
Страница 601: ...588 ...
Страница 602: ...589 ...
Страница 603: ...590 ...