229
Learning Advanced Features
Code
Description
KEB I Gain
Sets the gain value to maintain the operation until the frequency stops
during the kinetic energy buffering operation.
CON-83
KEB Acc Time
Sets the acceleration time for the frequency reference when the inverter’s
operation becomes normal after the kinetic energy buffering operation.
Note
•
The KEB functions may perform differently depending on the size of the loads. The KEB
Gains can be set for a better performance.
•
If a low voltage trip occurs after a power interruption, it indicates the load inertia and level
are high. In such cases, the KEB functions can be performed better by increasing the KEB
I Gain and the KEB Slip Gain.
•
If motor vibration or torque variation occurs during the KEB function operation after power
interruptions, the KEB functions can be performed better by increasing the KEB P Gain or
decreasing the KEB I Gain.
5.24 Anti-hunting Regulation (Resonance Prevention)
This function is used to prevent the hunting of a V/F controlled fan or motor caused by
current distortion or oscillation, due to mechanical resonance or other reasons.
Group Code
Name
LCD Display
Parameter Setting Setting Range
Unit
CON
13
Enable or
disable anti-
hunting
regulation
(resonance
prevention)
AHR Sel
1
Yes
0 No
-
1 Yes
Depending on the duration of instantaneous power interruptions and the amount of load inertia,
a low voltage trip may occur even during a kinetic energy buffering operation. Motors may
vibrate during kinetic energy buffering operation for some loads, except for variable torque loads
(for example, fan or pump loads).
Содержание LSLV-H100 Series
Страница 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 35: ...Installing the Inverter 22 ...
Страница 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Страница 181: ...168 Learning Advanced Features PID Command Block ...
Страница 182: ...169 Learning Advanced Features ...
Страница 183: ...170 Learning Advanced Features PID Feedback Block ...
Страница 184: ...171 Learning Advanced Features PID Output Block ...
Страница 185: ...172 Learning Advanced Features PID Output Mode Block ...
Страница 198: ...185 Learning Advanced Features EPID1 Control block ...
Страница 199: ...186 Learning Advanced Features EPID2 Control block ...
Страница 220: ...207 Learning Advanced Features ...
Страница 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Страница 506: ...Table of Functions 493 ...
Страница 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Страница 549: ...Troubleshooting 536 ...
Страница 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 570: ...Technical Specification 557 110 185 kW 3 phase ...
Страница 601: ...588 ...
Страница 602: ...589 ...
Страница 603: ...590 ...