Learning Advanced Features
If the inverter output current is lower than the current set at BAS-14 (Noload Curr), the
output voltage must be reduced as low as the level set at ADV-51 (Energy Save). The
voltage before the energy saving operation starts will become the base value of the
percentage. Manual energy saving operation will not be carried out during acceleration and
deceleration.
Group Code Name
LCD Display Parameter Setting
Setting Range
Unit
ADV
50
Energy saving
operation
E-Save
Mode
1
Manual
0
None
-
1
Manual
2
Auto
51
Energy saving
amount
Energy
Save
30
0
–30
%
5.26.2 Automatic Energy Saving Operation
The inverter finds the optimal energy saving point for the time set at ADV-52 based on the
rated motor current and the voltage output. The Energy saving operation is effective for the
normal duty operations. It does operate when the load level is more than 80% of the rated
motor current.
Group Code
Name
LCD Display
Parameter Setting Setting Range Unit
ADV
50
Energy saving
operation
E-Save Mode 2
Auto
0
–2
-
52
Energy saving
point search time
E-Save Det T 20.0
0.0
–100.0
Sec
If the operation frequency is changed, or acceleration or deceleration is carried out during an
energy saving operation, the actual Acc/Dec time may take longer than the set time due to the
time required to return to general operations from the energy saving operation.
Содержание LSLV-H100 Series
Страница 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 35: ...Installing the Inverter 22 ...
Страница 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Страница 181: ...168 Learning Advanced Features PID Command Block ...
Страница 182: ...169 Learning Advanced Features ...
Страница 183: ...170 Learning Advanced Features PID Feedback Block ...
Страница 184: ...171 Learning Advanced Features PID Output Block ...
Страница 185: ...172 Learning Advanced Features PID Output Mode Block ...
Страница 198: ...185 Learning Advanced Features EPID1 Control block ...
Страница 199: ...186 Learning Advanced Features EPID2 Control block ...
Страница 220: ...207 Learning Advanced Features ...
Страница 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Страница 506: ...Table of Functions 493 ...
Страница 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Страница 549: ...Troubleshooting 536 ...
Страница 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 570: ...Technical Specification 557 110 185 kW 3 phase ...
Страница 601: ...588 ...
Страница 602: ...589 ...
Страница 603: ...590 ...