162
Learning Advanced Features
Note
•
Normal PID output (PID OUT) is bipolar and is limited by PID-46 (PID Limit Hi) and PID-
47 (PID Limit Lo) settings. DRV-20 (MaxFreq) value equals a 100% of PID OUT.
•
The following are the variables used in PID operation, and how they are calculated:
-
Unit MAX = PID Unit 100% (PID-68)
-
Unit Min = (2xPID Unit 0% (PID-67)
–PID Unit 100%)
-
Unit Default = (PID Unit 100%-PID Unit 0%)/2
-
Unit Band = Unit 100%-Unit 0%
•
PID control may be utilized for the following operations:
Soft fill, auxiliary PID reference compensation, MMC, flow compensation, pipe breakage
detection
•
During a PID operation, the PID output becomes the frequency reference. The inverter
accelerates or decelerates to the frequency reference based on the Acc/Dec times.
PID Basic Operation Setting Details
Code
Description
PID-01 PID Sel
Sets the code to ‘1 (Yes)’ to select functions for the process PID.
PID-03 PID Output
Displays the existing output value of the PID controller. The unit, gain,
and scale that were set in the PID group are applied on the display.
PID-04 PID Ref
Value
Displays the existing reference value set for the PID controller. The unit,
gain, and scale that were set in the PID group are applied on the
display.
PID-05 PID Fdb
Value
Displays the latest feedback value of the PID controller. The unit, gain,
and scale that were set in the PID group are applied on the display.
PID-06 PID Err
Value
Displays the differences between the existing reference and the
feedback (error value). The unit, gain, and scale that were set in the PID
group are applied on the display.
PID-10 PID Ref 1
Src
Selects the reference input for the PID control. If the V1 terminal is set
to a PID feedback source (PID F/B Source), the V1 terminal cannot be
set to the PID reference source (PID Ref Source). To set V1 as a
reference source, change the feedback source.
Setting
Function
0
Keypad
Keypad
1
V1
-10-10 V input voltage terminal
3
V2
I2 analog input terminal
When the analog voltage/current input terminal
selection switch (SW4) at the terminal block is set
to I (current), input 0-20 mA current. If it is set to V
(voltage), input 0
–10 V.
4
I2
Содержание LSLV-H100 Series
Страница 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 35: ...Installing the Inverter 22 ...
Страница 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Страница 181: ...168 Learning Advanced Features PID Command Block ...
Страница 182: ...169 Learning Advanced Features ...
Страница 183: ...170 Learning Advanced Features PID Feedback Block ...
Страница 184: ...171 Learning Advanced Features PID Output Block ...
Страница 185: ...172 Learning Advanced Features PID Output Mode Block ...
Страница 198: ...185 Learning Advanced Features EPID1 Control block ...
Страница 199: ...186 Learning Advanced Features EPID2 Control block ...
Страница 220: ...207 Learning Advanced Features ...
Страница 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Страница 506: ...Table of Functions 493 ...
Страница 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Страница 549: ...Troubleshooting 536 ...
Страница 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 570: ...Technical Specification 557 110 185 kW 3 phase ...
Страница 601: ...588 ...
Страница 602: ...589 ...
Страница 603: ...590 ...