208
Learning Advanced Features
In the graph above, Pipe Break occurs if the feedback is smaller than the value calculated
by multiplying the two values set at PID-04 and PRT-61(PID-04 x PRT-61) at the inverter
’s
maximum output (when PID output is the maximum set value, or the inverter is running at
the frequency set at DRV-20).
5.20 Pre-heating Function
This function uses current to heat up the motor or pump to avoid the motor or the pump
freezing when they are not in operation.
Group Code
Name
LCD Display
Parameter Setting
Setting Range Unit
AP2
48
Initial heating
output current
Pre Heat Level
20
1
–100
%
49
Initial heating
output duty
Pre Heat Duty
30
1
–100
%
50
DC input delay
time
DC Inj Delay T
60.0
0.0
–600.0
sec
IN
65
–
71
Terminal block
input 1
–7
P1
–7 Define
44
Pre Heat
-
Initial Heating Setting Details
Code
Description
AP2-48 Pre Heat Curr
Sets the current to be used for initial heating. Sets the current to
motor no-load current % value.
AP2-49 Pre Heat Duty
Sets the duty (time) for the current to be used for initial heating, from
10 seconds to % value.
AP2-50 DC Inj Delay
T
Sets a certain delay time to prevent from an over current trip that may
occur when a DC input is performed after the inverter Free-Run stop.
IN-65
–71 P1–7 Define Performs the Pre Heat function if the Pre Heat (44) terminal is set.
The initial heating function continually operates when the set multi-function input terminal is
on and until the inverter command is on. If an inverter command is input while the initial
heating function is operating, the inverter starts operation immediately.
Содержание LSLV-H100 Series
Страница 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 35: ...Installing the Inverter 22 ...
Страница 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Страница 181: ...168 Learning Advanced Features PID Command Block ...
Страница 182: ...169 Learning Advanced Features ...
Страница 183: ...170 Learning Advanced Features PID Feedback Block ...
Страница 184: ...171 Learning Advanced Features PID Output Block ...
Страница 185: ...172 Learning Advanced Features PID Output Mode Block ...
Страница 198: ...185 Learning Advanced Features EPID1 Control block ...
Страница 199: ...186 Learning Advanced Features EPID2 Control block ...
Страница 220: ...207 Learning Advanced Features ...
Страница 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Страница 506: ...Table of Functions 493 ...
Страница 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Страница 549: ...Troubleshooting 536 ...
Страница 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 570: ...Technical Specification 557 110 185 kW 3 phase ...
Страница 601: ...588 ...
Страница 602: ...589 ...
Страница 603: ...590 ...