238
Learning Advanced Features
5.28 Auto Restart Settings
When inverter operation stops due to a fault and a fault trip is activated, the inverter
automatically restarts based on the parameter settings.
Group Code Name
LCD Display
Parameter
Setting
Setting Range
Unit
PRT
08
Select start at trip reset
RST Restart
11
-
-
09
Auto restart count
Retry Number
6
0
–10
-
10
Auto restart delay time
Retry Delay
1.0
0.1
–60.0
sec
CON
71
Select speed search
operation
Speed Search
-
0000
–1111
bit
72
Speed search startup
current
SS Sup-
Current
90
70
–120
%
73
Speed search
proportional gain
SS P-Gain
100
0
–9999
74
Speed search integral
gain
SS I-Gain
200
0
–9999
75
Output block time
before speed search
SS Block Time
1.0
0.0
–60.0
sec
Auto Restart Setting Details
Code
Description
PRT-08
RST Restart
The Reset restart function can be performed by one of the two different
types. If the top segment is turned on, it indicates the function is on. If
the bottom segment is turned on, it indicates the function is off.
Type
Bit On
Bit Off
Содержание LSLV-H100 Series
Страница 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 35: ...Installing the Inverter 22 ...
Страница 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Страница 181: ...168 Learning Advanced Features PID Command Block ...
Страница 182: ...169 Learning Advanced Features ...
Страница 183: ...170 Learning Advanced Features PID Feedback Block ...
Страница 184: ...171 Learning Advanced Features PID Output Block ...
Страница 185: ...172 Learning Advanced Features PID Output Mode Block ...
Страница 198: ...185 Learning Advanced Features EPID1 Control block ...
Страница 199: ...186 Learning Advanced Features EPID2 Control block ...
Страница 220: ...207 Learning Advanced Features ...
Страница 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Страница 506: ...Table of Functions 493 ...
Страница 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Страница 549: ...Troubleshooting 536 ...
Страница 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 570: ...Technical Specification 557 110 185 kW 3 phase ...
Страница 601: ...588 ...
Страница 602: ...589 ...
Страница 603: ...590 ...