163
Learning Advanced Features
Code
Description
5
Int. 485
RS-485 input terminal
7
FieldBus
Communication command via a communication
option card
8
Pulse
TI Pulse input terminal (0-32 kHz Pulse input)
9
E-PID
Output
External PID output
10
V3
V3 analoge input terminal of Extension IO option
When the analog voltage/current input terminal
selection switch (SW2) at the terminal block is set
to I3(current), input 0-20 mA current. If it is set to
V3 (voltage), input 0
–10 V.
11
I3
PID-11 PID Ref Set
A reference value can be entered if the PID reference type (PID-10) is
set to ‘0 (Keypad)’.
PID-12 PID
Ref1AuxSrc
Selects the external input source to be used as the reference for a PID
control. If an external input source is selected, the reference is
determined using the input value at the source (set at PID-10) and the
value set at PID-13 PID Ref1AuxMod.
Setting
Function
0
None
Not used
1
V1
-10-10 V input voltage terminal
3
V2
I2 analog input terminal
[If the analog voltage/current input terminal
selection switch (SW4) at the terminal block is set
to I (current), input 0-20 mA current. If it is set to V
(voltage), input 0
–10 V]
4
I2
6
Pulse
TI Pulse input terminal (0-32 kHz Pulse input)
7
Int. 485
RS-485 input terminal
8
FieldBus
Communication command via a communication
option card
10
EPID1
Output
External PID 1 Output
11
EPID1
Fdb Val
External PID 1 feedback value
12
V3
V3 analog input terminal of Extension IO option
When the analog voltage/current input terminal
selection switch (SW2) at the terminal block is set
to I3 (current), input 0-20 mA current. If it is set to
V3 (voltage), input 0
–10 V.
13
I3
PID-13 PID Ref1
AuxMod
PID-13 (PID Ref1) provides formulas to calculate the reference 1 value.
If PID-
12 (PID RefAuxSrc) is set to any other value than ‘None,’ the final
reference 1 value is calculated using the input value at the source (set
at PID-10) and the input value set at PID-12).
Setting
Содержание LSLV-H100 Series
Страница 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 35: ...Installing the Inverter 22 ...
Страница 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Страница 181: ...168 Learning Advanced Features PID Command Block ...
Страница 182: ...169 Learning Advanced Features ...
Страница 183: ...170 Learning Advanced Features PID Feedback Block ...
Страница 184: ...171 Learning Advanced Features PID Output Block ...
Страница 185: ...172 Learning Advanced Features PID Output Mode Block ...
Страница 198: ...185 Learning Advanced Features EPID1 Control block ...
Страница 199: ...186 Learning Advanced Features EPID2 Control block ...
Страница 220: ...207 Learning Advanced Features ...
Страница 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Страница 506: ...Table of Functions 493 ...
Страница 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Страница 549: ...Troubleshooting 536 ...
Страница 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 570: ...Technical Specification 557 110 185 kW 3 phase ...
Страница 601: ...588 ...
Страница 602: ...589 ...
Страница 603: ...590 ...