190
Learning Advanced Features
5.12 Flow Compensation
In a system with a pipeline, longer pipes and higher flow rate cause greater pressure loss. A
flow compensation operation can compensate for pressure loss by increasing the volume of
the PID reference.
Group Code
Name
LCD Display
Parameter Setting Setting Range
Unit
AP1
30
Flow Comp
function options
Flow Comp Sel -
0
No
-
1
Yes
31
Max Comp
amount
Max Comp
Value
-
0
–Unit Band
-
Flow Compensation Setting Details
Code
Description
AP1-30 Flow
Comp Sel
Sets the Flow Compensation function options.
AP1-31 Max
Comp Value
Sets the maximum compensation volume. This function is based on a PID
operation. The volum
e
is given the same unit used for the PID reference.
Longer pipes cause the actual pressure to decrease, which in turn increases the difference
between the pressure reference and the actual pressure. When the pipe lengths are equal
in two different systems, more pressure loss is caused in the system with greater flow. This
explains the pressure difference between (A) and (B) in the figure (when the flows are
different). To compensate for the pressure loss above, the value of AP1-31 is set to the
maximum volume of compensation when the inverter has the maximum frequency, and
adds to the PID reference after calculating compensation volume based on the output
frequency.
The final PID reference=PID-11+Compensation amount, and compensation amount is
shown below.
Содержание LSLV-H100 Series
Страница 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 35: ...Installing the Inverter 22 ...
Страница 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Страница 181: ...168 Learning Advanced Features PID Command Block ...
Страница 182: ...169 Learning Advanced Features ...
Страница 183: ...170 Learning Advanced Features PID Feedback Block ...
Страница 184: ...171 Learning Advanced Features PID Output Block ...
Страница 185: ...172 Learning Advanced Features PID Output Mode Block ...
Страница 198: ...185 Learning Advanced Features EPID1 Control block ...
Страница 199: ...186 Learning Advanced Features EPID2 Control block ...
Страница 220: ...207 Learning Advanced Features ...
Страница 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Страница 506: ...Table of Functions 493 ...
Страница 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Страница 549: ...Troubleshooting 536 ...
Страница 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 570: ...Technical Specification 557 110 185 kW 3 phase ...
Страница 601: ...588 ...
Страница 602: ...589 ...
Страница 603: ...590 ...