89
Learning Basic Features
Group Code Name
LCD Display
Parameter
Setting
Setting Range
Unit
16
Rotation direction
options
V1 Inverting 0
No
0
–1
-
17
V1 Quantizing level
V1
Quantizing
0.04
0.00*, 0.04
–
10.00
%
*
Quantizing is disabled if ‘0’ is selected.
Code
Description
IN-01 Freq at
100%
Configures the frequency reference at the maximum input voltage when a
potentiometer is connected to the control terminal block. A frequency set
with code IN-01 becomes the maximum frequency only if the value set in
code IN-11 (or IN-15) is 100 (%).
•
Set code IN-01 to 40.00 and use default values for codes IN-02
–IN-
16. Motor will run at 40.00 Hz when a 10 V input is provided at V1.
•
Set code IN-11 to 50.00 and use default values for codes IN-01
–IN-
16. Motor will run at 30.00 Hz (50% of the default maximum
frequency
–60 Hz) when a 10 V input is provided at V1.
IN-05 V1
Monitor[V]
Configures the inverter to monitor the input voltage at V1.
IN-07
V1 Filter
V1 Filter may be used when there are large variations between reference
frequencies. Variations can be mitigated by increasing the time constant,
but this requires an increased response time.
The value t (time) indicates the time required for the frequency to reach
63% of the reference, when external input voltages are provided in multiple
steps.
[V1 Filter ]
IN-08 V1 volt x1
–
These parameters are used to configure the gradient level and offset
Содержание LSLV-H100 Series
Страница 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 35: ...Installing the Inverter 22 ...
Страница 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Страница 181: ...168 Learning Advanced Features PID Command Block ...
Страница 182: ...169 Learning Advanced Features ...
Страница 183: ...170 Learning Advanced Features PID Feedback Block ...
Страница 184: ...171 Learning Advanced Features PID Output Block ...
Страница 185: ...172 Learning Advanced Features PID Output Mode Block ...
Страница 198: ...185 Learning Advanced Features EPID1 Control block ...
Страница 199: ...186 Learning Advanced Features EPID2 Control block ...
Страница 220: ...207 Learning Advanced Features ...
Страница 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Страница 506: ...Table of Functions 493 ...
Страница 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Страница 549: ...Troubleshooting 536 ...
Страница 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 570: ...Technical Specification 557 110 185 kW 3 phase ...
Страница 601: ...588 ...
Страница 602: ...589 ...
Страница 603: ...590 ...