Learning Advanced Features
Code
Description
inverter heat sink temperature is higher than its set
value, the cooling fan operates automatically
regardless of its operation status.
1
Always On
Cooling fan runs constantly if the power is supplied to
the inverter.
2
Temp
Control
With power connected and the run operation
command on: if the setting is in Temp Control, the
cooling fan will not operate unless the temperature in
the heat sink reaches the set temperature.
Note
Despite setting ADV-
64 to ‘0 (During Run)’, if the heat sink temperature reaches a set level by
current input harmonic wave or noise, the cooling fan may run as a protective function.
A capacity of 110 kW or more has a small built-in fan installed to cool the internal temperature.
The internal fan controls on / off in conjunction with the operation command of the inverter main
control fan
5.33 Input Power Frequency and Voltage Settings
Select the frequency for inverter input power. If the frequency changes from 60 Hz to 50 Hz,
all other frequency (or RPM) settings, including the maximum frequency, base frequency,
etc., will change to 50 Hz. Likewise, changing the input power frequency setting from 50 Hz
to 60 Hz will change all related function item settings from 50 Hz to 60 Hz.
Group Code Name
LCD Display
Parameter Setting Setting Range Unit
BAS
10
Input power frequency 60/50 Hz Sel
0
60 Hz
0
–1
-
Set Inverter input power voltage. Low voltage fault trip level changes automatically to the
set voltage standard.
Group Code
Name
LCD Display Parameter Setting
Setting Range
Unit
BAS
19
Input
power
voltage
AC Input
Volt
200 Type
220 170
–240
V
400 Type
380
320
–480 0.75~90kW
320-550
110~500kW
Содержание LSLV-H100 Series
Страница 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 35: ...Installing the Inverter 22 ...
Страница 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Страница 181: ...168 Learning Advanced Features PID Command Block ...
Страница 182: ...169 Learning Advanced Features ...
Страница 183: ...170 Learning Advanced Features PID Feedback Block ...
Страница 184: ...171 Learning Advanced Features PID Output Block ...
Страница 185: ...172 Learning Advanced Features PID Output Mode Block ...
Страница 198: ...185 Learning Advanced Features EPID1 Control block ...
Страница 199: ...186 Learning Advanced Features EPID2 Control block ...
Страница 220: ...207 Learning Advanced Features ...
Страница 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Страница 506: ...Table of Functions 493 ...
Страница 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Страница 549: ...Troubleshooting 536 ...
Страница 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 570: ...Technical Specification 557 110 185 kW 3 phase ...
Страница 601: ...588 ...
Страница 602: ...589 ...
Страница 603: ...590 ...