Learning Advanced Features
Note
When the maximum frequency value is high, output frequency deviation may result due to
analog input variation and deviations in the calculations.
Auxiliary Reference Operation Ex #3
V1 is Main Frequency and I2 is Auxiliary Frequency
•
Main frequency: V1 (frequency command setting to 5 V and is set to 30 Hz)
•
Maximum frequency setting (DRV-20): 400 Hz
•
Auxiliary frequency (BAS-01): I2[Display by percentage (%) or auxiliary frequency (Hz)
depending on the operation setting condition]
•
Auxiliary reference gain (BAS-03): 50%
•
IN-01
–32: Factory default
Example: An input current of 10.4 mA is applied to I2, with the frequency corresponding to
20 mA of 60 Hz. The table below shows auxiliary frequency Aas 24 Hz (=60[Hz]x{(10.4[mA]-
4[mA])/(20[mA]-4[mA])} or 40% (=100[%] x {(10.4[mA] - 4[mA]) /(20 [mA] - 4[mA])}.
Setting*
Calculating final command frequency**
0
M[Hz]+(G[%]*A[Hz])
30 Hz(M)+(50%(G)x24 Hz(A))=42 Hz
1
M[Hz]*(G[%]*A[%])
30 Hz(M)x(50%(G)x40%(A))=6 Hz
2
M[Hz]/(G[%]*A[%])
30 Hz(M)/(50%(G)x40%(A))=150 Hz
3
M[Hz]+{M[Hz]*(G[%]*A[%])}
30 Hz(M)+{30[Hz]x(50%(G)x40%(A))}=36 Hz
4
M[Hz]+G[%]*2*(A[%]-50[%])[Hz]
30 Hz(M)+50%(G)x2x(40%(A)
–50%)x60 Hz=24
Hz
5
M[HZ]*{G[%]*2*(A[%]-50[%])}
30 Hz(M)x{50%(G)x2x(40%(A)
–50%)}=-3
Hz( Reverse )
6
M[HZ]/{G[%]*2*(A[%]-50[%])}
30 Hz(M)/{50%(G)x2x(60%
–40%)}=-300
Hz( Reverse )
7
M[HZ]+M[HZ]*G[%]*2*(A[%]-
50[%])
30 Hz(M)+30 Hz(M)x50%(G)x2x(40%(A)
–
50%)=27 Hz
*
M: main frequency reference (Hz or rpm)/G: auxiliary reference gain (%)/A: auxiliary
frequency reference (Hz or rpm) or gain (%).
**If the frequency setting is changed to rpm, it is converted to rpm instead of Hz.
Содержание LSLV-H100 Series
Страница 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 35: ...Installing the Inverter 22 ...
Страница 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Страница 181: ...168 Learning Advanced Features PID Command Block ...
Страница 182: ...169 Learning Advanced Features ...
Страница 183: ...170 Learning Advanced Features PID Feedback Block ...
Страница 184: ...171 Learning Advanced Features PID Output Block ...
Страница 185: ...172 Learning Advanced Features PID Output Mode Block ...
Страница 198: ...185 Learning Advanced Features EPID1 Control block ...
Страница 199: ...186 Learning Advanced Features EPID2 Control block ...
Страница 220: ...207 Learning Advanced Features ...
Страница 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Страница 506: ...Table of Functions 493 ...
Страница 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Страница 549: ...Troubleshooting 536 ...
Страница 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 570: ...Technical Specification 557 110 185 kW 3 phase ...
Страница 601: ...588 ...
Страница 602: ...589 ...
Страница 603: ...590 ...