Firmware
≤
02.00 - DMS 2.1 EN - 03/2011
L
361
8400 motec | Software Manual
Application examples
Sequence control
Special features:
In partial-load operational range, (e.g. during the night), it can be operated with a small
unit and thus energy can be saved.
For pump 2, both a second 8400 motec and a starter or contactor can be used.
[13-2] Level curve
Example parameter setting:
V
IN1
(pump 1) = 0 ... 50 %
V
IN2
(pump 2) = 0 % / 50 %
9
,1
287
9
9
,1
9
727$/
9
,1
287
9
9
,1
9
727$/
Parameter
Info
Setting
Info
Settings for motor control and device control
Motor control
8: VFCplus: V/f quadr
V/f characteristic control (VFCplus)
Auto-start option
0x01
Starting performance of the controller:
Inhibit after mains connection.
Auto-start option "Inhibit at power-
Auto-DCB: Threshold
100 rpm
Automatic DC-injection braking (Auto-
Auto-DCB: Hold time
0.0 s
DC-injection braking deactivated.
Assignment of the input/output terminals
Control mode
The pre-assignment is changed through
the following parameter setting.
LS_DigitalOutput:bRelay
220:
L_GP_DigitalDelay1_
bOut
The relay is triggered by the binary delay
element.
The relay causes pump 2 to be released
(delayed).
LA_NCtrl: bSetSpeedCcw
0: Not connected
Now, a reversal or rotation via digital
input DI4 is not possible anymore.
Analog input
AINx: Configuration
2: 4...+20mA
Input signal is current signal
4 mA ... 20 mA.
Resp. to open circuit AINx
0: No Reaction
Open-circuit monitoring is deactivated.
Setpoint generator
Acceleration time - main setpoint
20 s
Deceleration time - main
setpoint
20 s