Firmware
≤
02.00 - DMS 2.1 EN - 03/2011
L
317
8400 motec | Software Manual
Function library
L_MPot_1
12.1.2
Deactivate motor potentiometer
When the motor potentiometer is deactivated by setting
bInAct
to TRUE, the
nOut_a
output signal responds according to the function selected in
.
[12-2] Example: Deactivation of the motor potentiometer if
= "1: Deceleration to 0"
bUp
bDown
bInact
Function
FALSE
FALSE
FALSE
The
nOut_a
output signal remains unchanged.
TRUE
FALSE
The
nOut_a
output signal runs to its upper limit value (
nHighLimit
).
FALSE
TRUE
The
nOut_a
output signal runs to its lower limit value (
nLowLimit
).
TRUE
TRUE
The
nOut_a
output signal remains unchanged.
-
-
TRUE
The motor potentiometer function is deactivated. The
nOut_a
output signal responds according to the function selected via
Function
.
When the motor potentiometer is deactivated,
nOut_a
is reduced to 0 % with the deceleration time
wTif
.
If it is activated again,
nOut_a
is increased again to
nLowLimit
with the acceleration time
wTir
.
nOut
_a
t
t
T
R
U
E
F
A
L
SE
bUp
t
T
R
U
E
F
A
L
SE
bD
own
nHi
gh
Limit
nLo
w
Limit
0
w
Tir
w
Tif
w
Tir
t
T
R
U
E
F
A
L
SE
bI
n
Ac
t
w
Tif
w
Tif
0
1