Firmware
≤
02.00 - DMS 2.1 EN - 03/2011
L
293
8400 motec | Software Manual
Parameter reference
Parameter list | C00990
C00990
C00991
C00992
C00994
C01082
Parameter | Name:
C00990 | Flying restart fct.: Activation
Data type: UNSIGNED_8
Index: 23585
d
= 5C21
h
Switch on /activate flying restart circuit for non-feedback drive systems
Selection list
(Lenze setting printed in bold)
0 Off
1 On
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00991 | Flying restart fct.: Process
Data type: UNSIGNED_16
Index: 23584
d
= 5C20
h
Selection of the speed search range for the flying restart function
Selection list
(Lenze setting printed in bold)
5 -n...+n | Last output frequency
6 -n...+n | Actual setpoint frequency
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00992 | Flying restart: Start frequency
Data type: INTEGER_16
Index: 23583
d
= 5C1F
h
Selection of the starting value for the flying restart function
Setting range
(min. value | unit | max. value)
Lenze setting
-200
Hz
200
10 Hz
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00994 - Flying restart fct.: Current
Data type: INTEGER_16
Index: 23581
d
= 5C1D
h
Current to be injected during the flying restart process
• 100 %
≡
rated motor current (
).
• The flying restart current should amount to 10 ... 25 % of the rated motor current.
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
%
100.0
25.0 %
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C01082 | LS_WriteParamList: Execute Mode
Data type: UNSIGNED_8
Index: 23493
d
= 5BC5
h
: Selection of the activation method
Selection list
(Lenze setting printed in bold)
Info
0 by Execute
The writing of the parameter list is activated by a FALSE/
TRUE edge at the
bExecute
input.
1 by Input Select
The parameter list is written if a change is made at the
bSelectWriteValue_1
selection input and once when the
controller is initialised.
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1