8400 motec | Software Manual
Commissioning
Commissioning with the »Engineer«
24
L
Firmware
≤
02.00 - DMS 2.1 EN - 03/2011
6. Switch on voltage supply of the controller.
– Information on some operating states can be quickly obtained via the two-colored
LED display on the top of the device.
7. Establish a connection to the controller, e.g. via USB diagnostic adapter:
– Remove the cover of the diagnostic interface on the top of the device and connect
the USB diagnostic adapter to the diagnostic interface.
– Connect the USB diagnostic adapter to the PC via a free USB port.
3.3.3
Creating an »Engineer« project & going online
The following steps describe the standard procedure of creating a project using the
Select
component from catalogue
option. Here, you select the single components (controller,
motor, etc.) from selection lists.
1. Start the »Engineer«.
2. Create a new project by means of the
Start-up wizard
and the
Select component from
catalogue
option:
– In the
Component
dialog step, select the 8400 motec controller.
– Select the available communication option in the
device modules
dialog step.
– Select the "actuating drive speed" application in the
Application
dialog step.
– Select the other components (motor/gearbox) to be added to the project in the
Other
components
dialog step.
3.
Go online.
– After a successful connection to the controller, the following status is displayed in
the
Status line
:
4.
Download parameter set.
– This command serves to overwrite the current parameter settings in the controller
by parameter settings of the »Engineer« project.
You can find detailed information on the general use of the »Engineer« in the
online help which you can call with
[F1]
.
• In the chapter "Working with projects" all options of the
Start-up wizard
are
described in order to create a new »Engineer« project.