Firmware
≤
02.00 - DMS 2.1 EN - 03/2011
L
237
8400 motec | Software Manual
Parameter reference
Parameter list | C00010
C00010
C00011
12 Terminals 2: Jog1; Jog2; QSp; R/L
The technology application is controlled via the digital
input terminals of the controller:
• DI1 = fixed setpoint 1/3
• DI2 = fixed setpoint 2/3
• DI3 = quick stop
• DI4 = change of direction of rotation
• DI5 = manual release of holding brake (set operating
14 Terminals 11: R/L; DCB; MPotUp;
MPotDown
The technology application is controlled via the digital
input terminals of the controller:
• DI1 = change of direction of rotation
• DI2 = activate DC injection brake
• DI3 = motor potentiometer: Higher speed
• DI4 = motor potentiometer: Lower speed
• DI5 = manual release of holding brake (set operating
16 Terminals 16: Jog1; Jog2; R/QSP; L/
QSP
The technology application is controlled via the digital
input terminals of the controller:
• DI1 = fixed setpoint 1/3
• DI2 = fixed setpoint 2/3
• DI3 = CW rotation/quick stop
• DI4 = CCW rotation/quick stop
• DI5 = manual release of holding brake (set operating
40 Network (MCI/CAN)
The technology application is controlled via fieldbus
communication (depending on the available
communication unit).
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00007 | Control mode
Data type: UNSIGNED_16
Index: 24568
d
= 5FF8
h
Parameter | Name:
C00010 | Minimum analog setpoint
Data type: INTEGER_16
Index: 24565
d
= 5FF5
h
Lower limit for analog input
Setting range
(min. value | unit | max. value)
0.0
%
100.0
Subcodes
Lenze setting
Info
C00010/1
0.0 %
Min. analog setpoint
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00011 | Appl.: Reference speed
Data type: UNSIGNED_16
Index: 24564
d
= 5FF4
h
Setting the reference speed
• In the controller, all speed-related signals are processed to one reference variable in percent.
• Set a reference speed here that corresponds to 100 %.
Note:
This is not a maximum limitation!
All values in percent in the controller may be in the range of 0 ... 199.99 %.
Setting range
(min. value | unit | max. value)
Lenze setting
50
rpm
9999
1500 rpm
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1