8400 motec | Software Manual
Drive application
Interface description
156
L
Firmware
≤
02.00 - DMS 2.1 EN - 03/2011
Setpoint generator
• For a detailed functional description see FB
bSetSpeedCcw
BOOL
Change of direction of rotation
• For instance if a motor or gearbox is fixed laterally reversed to a machine part, but
the setpoint selection should still be executed for the positive direction of
rotation.
FALSE Direction of rotation to the right (Cw)
TRUE Direction of rotation to the left (Ccw)
bJogSpeed1
bJogSpeed2
BOOL
Selection inputs for fixed changeover setpoints (JOG setpoints) for the main setpoint
• A fixed setpoint for the setpoint generator can be activated instead of the main
setpoint via these selection inputs.
• The two selection inputs are binary coded, therefore you can select three fixed
setpoints.
• In the case of binary coded selection "0" (all inputs = FALSE or not assigned), main
setpoint
nMainSetValue_a
is active.
• The selection of the fixed setpoints is executed in
in [%] based on
the reference speed (
• For a detailed functional description see FB
bRFG_0
BOOL
Ramp function generator: Lead the main setpoint integrator to "0" within the
current Ti times
• For a detailed functional description see FB
TRUE The current value of the main setpoint integrator is led to "0" within
the Ti time set.
Motor potentiometer
Alternatively to the input signal
nMainSetValue_a
, the main setpoint can also be generated by a motor
potentiometer function.
• In the Lenze setting, the motor potentiometer function is deactivated.
• Activation is possible via
bMPotEnable
input.
• The behaviour of the motor potentiometer during switch-on of the drive system can be selected in
• For a detailed functional description see FB
bMPotUp
BOOL
Increasing the speed setpoint
TRUE Approach the upper speed limit value set in
with the
bMPotDown
BOOL
Decreasing the speed setpoint
TRUE Approach the lower speed limit value set In
with the
deceleration time set in
.
bMPotInAct
BOOL
Activating the inactive function
TRUE The speed setpoint behaves according to the inactive function set in
.
• In the Lenze setting, the speed setpoint is maintained.
bMPotEnable
BOOL
Activating the motor potentiometer function
• This input and
are OR'd.
TRUE The motor potentiometer function is active; the speed setpoint can
be changed via the
bMPotUp
and
bMPotDown
control inputs.
Identifier
Data type
Configuration parameters
Information/possible settings
Содержание 8400 motec Series
Страница 375: ...L 375 ...