How to carry out automatic motor parameter identification:
1. Inhibit the controller if it is enabled, e.g. via the
LOW signal at the RFR terminal.
2. Wait until the drive is at standstill.
3. Transfer the nameplate data to the following codes:
•
•
•
: Rated motor current (according to the connection method
/
)
•
: Rated motor frequency (according to the connection method
/
)
•
: Rated motor voltage (according to the connection method
/
)
•
: Motor cos
ϕ
4. Start motor parameter identification via the
device command.
5. Enable the controller again.
• Motor parameter identification starts.
• The motor parameter identification takes approx. 30 s.
• The identification is completed if the "0: Off / ready" message is displayed in
6. Inhibit controller again.
Note!
Motor parameter identification may be aborted by the controller if a special
motor (e.g. mid-frequency motor) is used or if there is a large deviation between
inverter and motor power.
Another cause for the abort of the motor parameter identification could be the
implausibility of the entered nameplate data, e.g. the entry P = 0 kW for the
motor power.