Delayed disconnection in partial-load operation ("Sleep Mode")
13.2
Delayed disconnection in partial-load operation ("Sleep Mode")
Task:
If the drive remains below a minimum load threshold for a longer period of time, the drive
is to be switched off for saving energy. If the setpoint exceeds the minimum load
threshold, the drive is to start again.
Solution:
The GP function "Analog comparison" (
) serves to monitor the setpoint
speed. As soon as it falls below the set switch-off threshold, the switch-off delay starts.
After the set delay time has expired, the drive switches off itself.
The switch-off delay is implemented with the GP function "Binary delay element"
(
As soon as the setpoint exceeds the switch-off threshold again, the drive restarts.
[13-3] Standard signal flow
Example parameter setting:
Digital
Delay
Compare
|IN1| < |IN2|
IN2
NSet
C00472/1
30 %
IN1
LA_NCtrl: bRFG_0
C00720/1
C00720/2
On delay
Off delay
LS_DigitalOutput: bRelay
bJog1
bJog2
nNSet_a
0
0
3
2
1
2
0
1
2
C00039/1
C
/2
00039
C
/2
00039
3
SetSpeedValueEff
bJogSpeed1
bJogSpeed2
nMainSetValue_a
C00680
Function
Parameter
Info
Setting
Info
Settings for device control
Auto-start option
0x00
Starting performance of the controller:
No inhibit after mains connection.
Assignment of the input/output terminals
LS_DigitalOutput:bRelay
220:
L_GP_DigitalDelay1_
bOut
The relay is triggered by the binary delay
element.
GP function "Analog comparison"
L_Compare_1: Fct.
6: |In1| < |In2|
Comparison operation:
|AIn1_Out| < |
L_GP_Compare1: nIn1_a
13: SetSpeedValueEff Comparison value 1 is the input value of
the setpoint generator
selected via the JOG inputs.
L_GP_Compare1: nIn2_a
20: nPar1_a
The comparison value 2 is selected via
the free parameter
LS_ParFree_a: Value 1
30.0 %
Selection of the comparison value 2
(switch-off threshold).