Mains phase failure monitoring
The drive controller has a simple mains-phase failure detection function with which a
mains phase failure can be detected under load.
In the case of power-adapted machines, approx. 50 % of the rated motor power must
be exceeded so that a main-phase failure can be detected.
If the mains phase failure monitoring is tripped:
– The error response set in
will be carried out (Lenze setting: "Warning").
– The "
Su02: Mains voltage switched-off
" error message is entered into the logbook.
Stop!
Under load, the mains input of a three-phase controller can be destroyed if the
device is only supplied by two phases (e.g. if a mains phase fails).
Note!
The failure of a mains phase can also generate an error message "