8400 motec | Software Manual
Basic functions
Parameter change-over
176
L
Firmware
≤
02.00 - DMS 2.1 EN - 03/2011
Entering further different values for the parameters (value set 2)
If required, you can set another set with values in the same manner in
which
serve to write the parameters.
8.1.3
Selecting a value set
The value set to be used is selected via the
bSelectWriteValue_1
selection input. This
selection input can be linked with another output signal via the configuration parameter
.
8.1.4
Activating the writing of the parameters
For writing the parameter list, two modes are available in
:
0: by Execute (Lenze setting)
The writing of the parameter list is activated by a FALSE-TRUE edge at the
bExecute
control input. This control input can be linked with another output signal via the
1: by Input Select
The parameter list is written if a change is made at the
bSelectWriteValue_1
selection
input and once when the controller is initialised.
The parameters are written one at a time every time the main program is executed until
the entire parameter list is processed. In case of an error, corresponding error messages are
output.
After successful completion
... the
bDone
output is set to TRUE.
The
bDone
output is automatically reset to FALSE if writing via
bExecute
is activated
again.
In the event of an error
... the
bDone
output remains set to FALSE and the
bFail
output is set to TRUE.
displays the number of the list entry at
which the error occurred (in connection with the selected value set).
If several errors occur at the same time, only the first incorrect list entry will be
displayed. Hence, after elimination of the displayed error and another activation, more
errors may be displayed.
The parameter list will always be processed from beginning to end, even if errors occur
in the meantime.
bSelectWriteValue_1 Value set used
FALSE
Value set 1 (
)
TRUE
Value set 2 (
)