8400 motec | Software Manual
Motor control (MCTRL)
Monitoring
5.13
Monitoring
Many monitoring functions that are integrated into the controller can detect errors and
thus protect the device/motor from damage or overload.
Detailed information on the individual monitoring functions can be found in the
following subchapters.
Parameterisable responses
If a monitoring function trips, the response set via the corresponding parameter is carried
out. The following responses can be selected:
"No response": Response/monitoring is deactivated.
"Fault": Change of the operating status by a pulse inhibit of the power output stage.
"Warning": Operating status of the controller remains unchanged. Only a message is
entered into the logbook of the controller.
Related topics:
Device state machine and device states
Diagnostics & error management
Error messages of the operating system
Parameter
Monitoring
Response
(Lenze setting)
Mains phase failure monitoring
Warning
Brake resistor monitoring (I2xt)
Fault
Motor temperature monitoring (PTC)
Fault
Encoder open-circuit monitoring
Fault
Undervoltage in the DC bus
Fault
Overvoltage in the DC bus
• The response to overvoltage is always "Fault".
• The response only takes place after the deceleration time set in
has elapsed (if the overvoltage is still present then).
Fault
Device overload monitoring (Ixt)
Warning
Warning