The power cords you provide must comply with the specifications listed in
Table 47 on page 136
.
NOTE:
In North America, AC power cords must not exceed 4.5 m
(approximately 14.75 ft) in length, to comply with National Electrical Code
(NEC) Sections 400-8 (NFPA 75, 5-2.2) and 210-52, and Canadian Electrical
Code (CEC) Section 4-010(3).
Table 47: Three-Phase Delta AC Power Cord Specifications
Cord or Cable Type
Plug
Color
Plug Type
Electrical
Rating
The cord or cable must be HAR compliant, IEC 60245 (designation
60245 IEC 53) or IEC 60227 (designation 60227 IEC 53); or meet
one of the following standards (North America): SV, SVE, SVO,
SVOO, SVT, SVTO, SVTOO, SP-2, SPE-2, SPT-2, NISP-2, NISPE-2,
NISPT-2, SP-3, SPE-3, SPT-3, SJ, SJE, SJO, SJOO, SJT, SJTO,
SJTOO, S, SE, SO, SOO, ST, STO, STOO
Blue
International
Electrotechnical
Commission (IEC) 60309
250 VAC, 60 A
Related
Documentation
AC Power Supply in a QFX3008-I Interconnect Device
•
•
Wiring Tray in a QFX3008-I Interconnect Device
•
AC Power Electrical Safety Guidelines
•
AC Power Disconnection Warning
•
General Electrical Safety Guidelines and Warnings
•
Connecting AC Power to a QFX3008-I Interconnect Device with Three-Phase Delta
Wiring Trays on page 183
AC Power Cord Specifications for a QFX3008-I Interconnect Device with Three-Phase
Wye Wiring Trays
Supported Platforms
QFX3000-G
Most sites distribute power through a main conduit that leads to frame-mounted power
distribution panels, one of which can be located at the top of the rack that houses the
device. An AC power cord connects each wiring tray to the power distribution panel.
WARNING:
The QFX3008-I Interconnect device is pluggable type A equipment
installed in a restricted-access location. It has a separate protective earthing
terminal provided on the chassis in addition to the grounding pin of the power
supply cord. This separate protective earthing terminal must be permanently
connected to earth.
Copyright © 2015, Juniper Networks, Inc.
136
QFX3000-G QFabric System Deployment Guide
Содержание QFX3000-G QFabric
Страница 12: ...Copyright 2015 Juniper Networks Inc xii QFX3000 G QFabric System Deployment Guide...
Страница 28: ...Copyright 2015 Juniper Networks Inc 2 QFX3000 G QFabric System Deployment Guide...
Страница 102: ...Copyright 2015 Juniper Networks Inc 76 QFX3000 G QFabric System Deployment Guide...
Страница 108: ...Copyright 2015 Juniper Networks Inc 82 QFX3000 G QFabric System Deployment Guide...
Страница 154: ...Copyright 2015 Juniper Networks Inc 128 QFX3000 G QFabric System Deployment Guide...
Страница 168: ...Copyright 2015 Juniper Networks Inc 142 QFX3000 G QFabric System Deployment Guide...
Страница 180: ...Copyright 2015 Juniper Networks Inc 154 QFX3000 G QFabric System Deployment Guide...
Страница 270: ...Copyright 2015 Juniper Networks Inc 244 QFX3000 G QFabric System Deployment Guide...
Страница 294: ...Copyright 2015 Juniper Networks Inc 268 QFX3000 G QFabric System Deployment Guide...
Страница 300: ...Copyright 2015 Juniper Networks Inc 274 QFX3000 G QFabric System Deployment Guide...
Страница 394: ...Copyright 2015 Juniper Networks Inc 368 QFX3000 G QFabric System Deployment Guide...
Страница 468: ...Copyright 2015 Juniper Networks Inc 442 QFX3000 G QFabric System Deployment Guide...
Страница 470: ...Copyright 2015 Juniper Networks Inc 444 QFX3000 G QFabric System Deployment Guide...
Страница 608: ...Copyright 2015 Juniper Networks Inc 582 QFX3000 G QFabric System Deployment Guide...
Страница 639: ...PART 5 Troubleshooting QFabric System Troubleshooting on page 615 613 Copyright 2015 Juniper Networks Inc...
Страница 640: ...Copyright 2015 Juniper Networks Inc 614 QFX3000 G QFabric System Deployment Guide...