Appendix 7: Specifications
Feature
Description
Current draw -
control panel
board assembly
120 mA (nominal).
Bell output
10.8 VDC to 12.5 VDC (UL/ULC applications).
10 VDC to 14 VDC (EN applications).
700 mA supervised (1 kΩ), current limited at 2 A.
Steady, pulsed, temporal 3, or temporal 4 cadences.
Short circuit detection (hardware and software).
Aux +
10.8 VDC to 12.5 VDC (UL/ULC applications).
10 VDC to 14 VDC (EN applications).
2 A current (shared with Corbus and PGM outputs).
600 mVp-p max. output ripple voltage.
Onboard programmable outputs.
PGM overcurrent protection.
Over voltage protection.
Battery
12 V sealed lead acid, rechargeable.
Maximum standby time: Refer to
"Aux loading and battery selection" on page 53
for each type of application.
Recharges to 80% in 72 hr.
Recharging rate: 400 mA (12 hours max.), 700 mA (24 hour backup).
24 hr (UL) backup time.
3 to 5 year lifespan.
Low battery trouble indication threshold 11.3 VDC.
12.5 V restore voltage.
Self-reseting FETs for short/overcurrent protection on the circuit board.
Internal clock locked to the internal Real Time Clock.
Main board current draw: HS3032/HS3128/HS3248 (no alternate communicator) standby 100 mA DC.
HS3032/HS3128/HS3248, (including plug-in communicator) standby 120 mA DC.
The standby battery does not automatically recharge on reconnection of the AC mains (external power supply) if
the battery terminal voltage is less than 9.6 VDC. The minimum energy level of the standby battery in a charged
state (as a percentage of the rated capacity for the range of batteries that can be used with the power supply) is
90% for 17 Ah batteries.
Environmental
operating
conditions
Temperature range: UL/ULC: 0°C to +49°C (32°F to 120°F), For EN50131 applications: -10˚C to +55˚C
Relative humidity: 5% to 93% RH non-condensing
The alarm panel is not suitable for use external to the supervised premises.
Alarm transmitter
equipment
Digital dialer integral to the main control board
Supports SIA and Contact ID
Complies with TS203 021-1, -2, -3 Telecom equipment requirements and EN50136-1, EN50136-2, ATS SP3,
DP2 (when used in conjunction with Ethernet and/or Cellular paths).
The integral Ethernet communication port and optional plug-in cellular module (models 3G9080, 3H9080,
LE9080 for UL/ULC and 3G9080-EU, GS9080 for EN50131 applications) can be installed in the same
enclosure and configured as primary or back-up, with AES 128-bit encryption.
Compliant with EN50136-1, EN50136-2 ATS configurations SP4, DP3.
- 317 -