Section 6: Programming
Trouble
indication
Trouble
indicator
digit
Possible
causes
Trouble description and possible solutions
All LEDs flash
together
Boot loader
failed
To fix this trouble, disconnect power from the communicator and then reconnect power to the communicator.
Red and yel-
low LEDs
flash together
Initialization
sequence
This trouble indicates the communicator is initializing. Wait for the communicator to establish a connection to all
programmed receivers. This process can take several minutes to complete.
Only green
LEDs flash
Hardware
default
jumper
This trouble indicates that the hardware default jumper is installed and must be removed.
Green LEDs
flash altern-
ating
Radio reset
or radion ini-
tialization
It this trouble persists, and the yellow LEDs flash 5 times, confirm that the SIM card is active.
[985] - Radio Initialization Status
The radio initialization status indicates the status of radio communication. It is displayed as an 8-digit toggle option, with each digit
indicating a task in the initialization process.
1. Radio power up
2. Received the SMS from C24 Communications
3. Radio reset
4. Radio attached to network
5. Receiver 1 initialized
6. Receiver 2 initialized
7. Receiver 3 initialized
8. Receiver 4 initialized
For example, the radio initialization status code 12-45--- indicates that radio has been powered up, it has received SMS signal from
C24 Communications, the radio is attached to the network, and receiver 1 has been initialized. This code would update to 12-45678
when receivers 2, 3, and 4 are initialized.
If the radio initialization status code does not indicate any problems, proceed with installation as per this manual. If troubles are
reported, reset the initialization process. If this action does not fix the problem, refer to the trouble shooting section in this manual.
The following table shows each digit position in the status code, each digit’s value and its assigned meaning in the eight-digit code:
Table 6-14: Radio Initialization Status - 1-8 bits completion
Bit
1
2
3
4
5
6
7
8
Not Completed
Completed
1
2
3
4
5
6
7
8
[986] - Options 4
[1] Remote Shutfown
Default (OFF)
[987] - Language Version
This section displays the current language version of the communicator.
[988] - DNS 1 IP
This section displays the IP address of DNS Server 1. This is useful when the unit is configured for DHCP and the IP address
assigned to the device by the DHCP Server is needed. This value is programmed in Section [007] or assigned by DHCP.
[989] - DNS 2 IP
This section will display the IP address of DNS Server 2. This is useful when the unit is configured for DHCP and the IP
address assigned to the device by the DHCP Server is needed. This value is programmed in section [008] or assigned by
DHCP.
[990] - Boot Loader Version
This section displays the current boot loader version of the communicator.
[991] - Firmware Version
This section displays the current firmware version of the device. Update worksheets with new version after a flash update is
completed.
- 154 -