Section 6: Programming
OFF: Wireless device faults do not sound the siren.
2 – Latching Troubles
ON: Troubles remain on the system until viewed via [*][2], even if they are restored. The trouble condition is cleared when the"Press
(*) to Acknowledge" option is selected within the [*][2] menu after the trouble has restored. The Trouble LED turns off unless other
troubles are present. The trouble is not cleared if the [*][2] menu times out before the [#] key is pressed.
OFF: Troubles are cleared once restored.
3 – Reserved
4 – Reserved
5 – Audible Bus Fault
ON: All module supervisory trouble conditions activate the siren.
OFF: Only zone expander supervisory trouble conditions while armed activate the siren.
6 – Duress Codes
ON: The duress code attribute can be enabled/disabled from the [*][5] menu. For
UK
BS8243 installations the default is off.
OFF: The duress code attribute is not programmable from the [*][5] menu.
7 – Temperature in Celsius
ON: Temperature is displayed in Celsius on LCD keypads.
OFF: Temperature is displayed in Fahrenheit on LCD keypads.
8 – Reset After Zone Activation
ON: Only a police code\sequential detection alarm requires a remote reset once the partition has been disarmed.
OFF: Any burglary alarm requires a remote reset once the partition has been disarmed.
[020] System Option 8
1 – Access Code Entry During Entry Delay
ON: During entry delay the alarm system can only be disarmed using a keyswitch or proximity tag. When the siren is active an access
code can still be used to disarm the system.
OFF: An access code can be used to disarm the system during entry delay.
EN
2 – EU Entry Procedure
ON: If an alarm occurs on a zone when entry delay is not active, the siren activates and the alarm is communicated immediately,
depending on the zone type tripped.
When entry delay is active, all burglary type alarms activate the siren, but communication of the alarm is delayed by 30 seconds.
When entry delay expires, the alarm is not communicated unless the siren has been active for at least 30 seconds.
Police code is not generated as a result of alarms triggered during entry delay, although the Burglary Verification Timer starts after
entry delay and the 30-second communication delay expire.
This feature is only active when the partition is armed.
OFF: Burglary alarms that occur during entry delay activate the siren and are communicated immediately. Two exceptions are if the
bell delay timer is programmed and if transmission delay is enabled for the zone in alarm. In both cases, the alarm follows the timer.
3 – [*][8] Access While Armed
ON: This option ensures [*][8] installer programming is accessible from a keypad on a disarmed partition while other partitions on the
system are still armed.
Note:
For UL listed installations, this option must be disabled.
OFF: [*][8] installer programming is not available when any partition on the system is armed. All partitions must be disarmed and the
siren must be off before [*][8] is accessible.
UK
4 – Remote Reset
ON: If an alarm occurs on a burglary zone, the system is locked out after disarming. It remains locked until a 5-digit reset code,
provided by the installer/central station, is keyed in. If a duress code is used to disarm the partition, the system is not locked out.
In the disarmed state, only Audible 24 Hour Burglary zones, Audible 24 Hour Latching Tamper zones, and Audible 24 Hour zone on
PGM 2 cause lockout.
- 115 -