Section 2: Installation
HS3032/HS3128/HS3248 in HSC3010C NA wiring diagram
This diagram shows the routing of power limited and non-power limited wiring inside the enclosure. The battery leads and AC cord
are non-power limited, all other wiring is power limited.
Figure 2-9: Panel wiring for HSC3010C
UA718
MICRO-B
PC LINK
USB TYPE A
PGM
CORBUS
AUX
BELL
DC
AUX
ZONE
ZONE
ZONE
ZONE
TELCO
ETHERNET
BATTERY
Callout
Description
1
Power limited wiring entry/exit point
2
Metal standoff
3
Tamper switch and mounting bracket
4
Plastic grommet strip (not supplied)
5
Power adapter
6
Cable tie (not supplied)
7
Power adapter mounting screws
8
DC wiring from power adapter to the alarm controller
9
Cabinet
10
PC board
11
Standoff
Mounting the HSC3010C
For HSC3010C installations, complete the following steps:
1. If mounting the power supply inside the cabinet, use supplied hardware.
Note:
Minimum 1/4-inch (6.4 mm) separation must be maintained at all points between battery/AC wiring and all other wiring
connections. Do not route any wiring over circuit boards. Maintain at least 1 inch (25.4 mm) separation.
2. Install the grommet strip (available separately – p/n 57000933) into the opening on back of cabinet.. Route the AC cable out of the
enclosure through the opening indicated in the diagram.
3. If mounting the power supply outside the enclosure, attach it to the wall using suitable hardware. Route DC wires into the
enclosure and secure them with cable ties.
4. Use metal standoff and screw in postion indcated. Ensure screw and standoff are tightly secured to establish earth ground
connection.
Note:
For ULC commercial fire applications, use enclosure model HSC3010CR.
- 19 -