Appendix 1: Reporting codes
Section #
Definition
Dialer
Direction*
Automatic Contact ID
Codes
SIA Auto Rep Codes**
[308]-[313]
Panel firmware update begin/ successful
MA/R
E(9)01-900
R(9)01-900
LB-0900
LS-0900
[308]-[313]
Panel firmware update fail
MA/R
E(9)02-900
LU-0900
[308]-[313]
Radio firmware update begin/successful
MA/R
E(9)03-902
R(9)03-902
LB-0000
LS-0000
[308]-[313]
Radio firmware update fail
MA/R
E(9)04-903
LU-0000
[308]-[321]
Panel power unit fail/restore
MA/R
E(3)14-000
R(3)14-000
YP-000
YQ-000
*
**
***
A/R = alarms/restores; T/R = tampers/restorers; O/C = openings/closings; MA/R = maintenance alarms/restores; T = test
transmissions
UUU = user number (user 001-1000). Note that for CID, enter 999 for user 1000. ZZZ/ZZZZ = zone number (001-248).
Zones and panic pendants are identified, wireless keys can be identified for openings and closings.
1.3 Contact ID & SIA Zone Alarm/Restore Event Codes
(as per SIA DCS: ‘Contact ID’ 01-1999):
The table below defines the meaning of all Contact ID and SIA zone alarm/restore event codes.
Zone Definition
SIA Auto Rep Codes
Contact ID Auto Rep Codes
Delay 1
BA-ZZZZ / BH-ZZZZ
E(1) 3A - ZZZ / R(1)3A- ZZZ
Delay 2
BA-ZZZZ / BH-ZZZZ
E(1) 3A - ZZZ / R(1)3A- ZZZ
Instant
BA-ZZZZ / BH-ZZZZ
E(1) 3A - ZZZ / R(1)3A- ZZZ
Interior
BA-ZZZZ / BH-ZZZZ
E(1) 3A - ZZZ / R(1)3A- ZZZ
Interior Stay/Away
BA-ZZZZ / BH-ZZZZ
E(1) 3A - ZZZ / R(1)3A- ZZZ
Delay Stay/Away
BA-ZZZZ / BH-ZZZZ
E(1) 3A - ZZZ / R(1)3A- ZZZ
Instant Stay/Away
BA-ZZZZ / BH-ZZZZ
E(1) 3A - ZZZ / R(1)3A- ZZZ
Interior Delay
BA-ZZZZ / BH-ZZZZ
E(1) 3A - ZZZ / R(1)3A- ZZZ
Day Zone
BA-ZZZZ / BH-ZZZZ
E(1) 3A - ZZZ / R(1)3A- ZZZ
Night Zone
BA-ZZZZ / BH-ZZZZ
E(1) 3A - ZZZ / R(1)3A- ZZZ
24-Hr. Burglary
BA-ZZZZ / BH-ZZZZ
E(1) 3A - ZZZ / R(1)3A- ZZZ
Delayed 24-Hr. Fire (Wireless)
FA-ZZZZ / FH-ZZZZ
E(1) 1A - ZZZ / R(1)1A - ZZZ
Standard 24-Hr. Fire (Wireless)
FA-ZZZZ / FH-ZZZZ
E(1) 1A - ZZZ / R(1)1A - ZZZ
24-Hr. Sprinkler
SA-ZZZZ / SH-ZZZZ
E(1) 13 - ZZZ / R(1)13 - ZZZ
24-Hr.Low Temperature
ZA-ZZZZ / ZH-ZZZZ
E(1) 59 - ZZZ / R(1)59-ZZZ
24-Hr High Temperature
KA-ZZZZ / KH-ZZZZ
E(1) 58 - ZZZ / R(1)58 - ZZZ
24-Hr. Latching Tamper
BA-ZZZZ / BH-ZZZZ
E(1) 3A - ZZZ / R(1)3A- ZZZ
24-Hr. Non Alarm (Walk Test Only)
BA-ZZZZ / BH-ZZZZ
E(1) 3A - ZZZ / R(1)3A- ZZZ
24-Hr. Non-latching Tamper
TA-ZZZZ / TR-ZZZZ
E(3) 83 - ZZZ / R(3)83 - ZZZ
24-Hr. Masking Trouble
UT-ZZZZ / UJ-ZZZZ
E(3) 8A - ZZZ / R38A-ZZZ
Momentary Keyswitch Arm (Walk Test Only)
BA-ZZZZ / BH-ZZZZ
E(1) 3A - ZZZ / R(1)3A- ZZZ
Maintained Keyswitch Arm (Walk Test Only)
BA-ZZZZ / BH-ZZZZ
E(1) 3A - ZZZ / R(1)3A- ZZZ
Momentary Keyswitch Disarm (Walk Test Only)
BA-ZZZZ / BH-ZZZZ
E(1) 3A - ZZZ / R(1)3A- ZZZ
- 294 -