Section 2: Installation
Callout Component
Description
6
AUX 1
10.8 VDC to 12.5 VDC, 3 A max. (UL/ULC applications).
Note:
Aux output shared with Corbus.
7
AUX2
10 VDC to 14 VDC, 3 A max. supervised (EN50131 applications)
8
Fuse
For EU models only; 20 mm, rated 250V / 3.15A slow blow; replace the fuse with the same type.
Note:
All circuits are classified for UL installations as power limited/Class II power limited, except for the battery leads which are not
power limited. Do not route any wiring over circuit boards. Maintain at least 1 in (25.4 mm) separation. A minimum of 0.25 in (6.4 mm)
separation must be maintained at all points between power limited wiring and all other non-power limited wiring. Inspect wiring and
ensure connections are correct before applying power.
Note:
Note: Do not connect power adapter to a receptacle controlled by a switch.
Corbus repeater
The HSM3204CX is a Corbus repeater and isolator module with four high current relay outputs. The module has an on-board power
supply to power Corbus.
Switching Mode Power Adapter
Model HS65WPSNA is required for UL/ULC listed installations. It can be installed inside or outside the metal enclosure, model
HSC3010C, cord connected to AC mains. For ULC Commercial Fire or ULC Commercial Burg Security Level IV applications use
model HS65WPSNAS, installed inside the metal enclosure model HSC3010CR or HSC3010C (using high voltage barrier kit),
hardwired connection to AC mains.
Primary Input: 120 VAC / 50 Hz / 1.7 A max.
Output: 18 VDC / 3.6 A max.
Model HS65WPS is required for CE/EN50131 certified applications. It shall be installed inside the metal cabinet model HSC3020C,
hardwired connections to AC mains (see wiring diagram below).
Primary Input: 230 VAC / 60 Hz / 1.7 A max.
Output: 18 VDC / 3.6 A max.
Note:
Fire and Security devices that require power from the HSM3204CX shall be UL/ULC (or cUL) listed for the intended application
and operate over the range 10.8 VDC to 12.5 VDC.
- 40 -