Section 6: Programming
seconds and another 30-second delay starts. A code is required to silence the alarm. A tamper or fault causes a fire trouble to log and
transmit.
Note:
The supervision options (NC, SEOL, DEOL, TEOL) do not affect the functionality of this zone. The restored state of this zone
type is 5k6, the alarm state is short, and the trouble state is open.
008 – Standard 24-Hour Fire
This zone is used with smoke detectors. The siren sounds instantly when the smoke detector is activated. If enabled, the
communicator immediately transmits the alarm to the monitoring station. A tamper or fault of this zone type causes a fire trouble to log
and transmit.
Note:
The supervision options (NC, SEOL, DEOL, TEOL) do not affect the functionality of this zone. The restored state of this zone
type is 5.6k, the alarm state is short and the trouble state is open.
009 – Instant Stay/Away
Commonly assigned to interior motion sensors. This zone type is bypassed when armed in Stay mode, but functions like an Instant
zone [003] when armed in Away mode.
010 – Interior Delay
Commonly assigned to interior motion sensors. When Away armed, this zone type functions like the Interior zone type. When Stay or
night armed, tripping the zone activates entry delay 1. Tripping this zone during exit delay does not cause the system to arm in Away
mode, as tripping a regular Delay type zone does.
011 – Day Zone
Commonly used in areas where immediate notification of entry is desired. When disarmed, tripping this zone activates the keypad
buzzer but does not log or report the event. When armed, tripping this zone activates the siren then logs and reports the event.
Note:
An alarm during exit delay causes the siren to activate and remain on when exit delay expires.
012 – Night Zone
Commonly assigned to interior motion detectors in areas accessed during the night. This zone functions like an Interior Stay/Away
zone [005] when armed using any method except the following: If Stay armed, this zone is bypassed; if armed using [*][1], this zone is
bypassed.
016 – Final Door Set (Non CP-01 panels only)
UK
This zone type does not use an exit timer (infinite exit delay). The door must be opened then closed to complete the arming
sequence. The arming method determines if infinite exit delay is applied. See the table below.
Note:
Disable Exit Delay Termination with this zone type.
Note:
If this zone type is bypassed, the alarm system cannot be Away armed.
Arming method
Infinite exit delay
Arming mode
User code
Y
Away
Keyswitch
Y
Away
Away key
Y
Away
Wireless key away
Y
Away
*0 arm
Y
Away
*9 arm
N
Stay
Stay key
N
Stay
Wireless key stay
N
Stay
Remote Access/SMS
Do not use
DLS arm
N
Away
No activity arming
N
Away
Note:
When Troubles/Open Zones Cancel Arming is enabled with this zone, any troubles or open zones on the system cancel arming
when the zone is tripped and restored.
Due to the potential energy requirements of infinite exit delay, wireless keypads MUST be powered by a transformer.
If a wireless key is used to away arm the system, the door must still be opened then closed to complete the arming sequence. The
indoor siren will activate until the exit delay has expired.
- 88 -