Section 6: Programming
Program 00 to disable this event transmission or FF to enable. See system test options for details on settings.
[027] Ethernet 2 Test Transmission
Default (00)
Program 00 to disable this event transmission or FF to enable. See system test options (previous page) for details on settings.
[028] Cellular Receiver 3 Test Transmission
Default (FF)
Program 00 to disable this event transmission or FF to enable. See system test options (previous page) for details on settings.
[029] Cellular Receiver 4 Test Transmission
Default (00)
Program 00 to disable this event transmission or FF to enable. See system test options (previous page) for details on settings.
Note:
The time interval (in minutes) between periodic tests is programmed in section [125] (Ethernet) and section [225] (cellular).
[030] FTC Restore
Default (FF)
Program 00 to disable this event transmission or FF to enable. This event will occur when an FTC Trouble on the system restores.
[095] SA Incoming Local Port
Default (03092)
Valid range: 00000 - 65535
[096] SA Outgoing Local Port
Default (03093)
Valid range: 00000 - 65535
Ethernet Receiver 1 Options
[101] Ethernet Receiver 1 Account Code
Default (0000000000)
The account code is used by the central station to distinguish between transmitters. This account code is used when transmitting
heartbeat signals to the central station receiver. Signals received from the panel will use the control panel account number. Valid
range: 0000000001-FFFFFFFFFE.
Note:
If Ethernet receiver 1 and cellular receiver 1 are programmed as the same receiver (IP and port number are identical), Ethernet
receiver 1 account code will be used.
[102] Ethernet Receiver 1 DNIS
Default (000000)
The Dialed Number Information Service (DNIS) is used in addition to the account code to identify the communicator module at the
central station. Valid range: 000000 - 099999. Value is entered as a leading 0 followed by the 5 digit DNIS. Format is Binary Coded
Decimal (BCD).
Note:
Each Ethernet/cellular receiver must be programmed with a unique DNIS.
[103] Ethernet Receiver 1 Address
Default (127.000.000.001)
The default address enables the communicator to operate in Unattended Mode.
Unattended mode is used when a receiver is not available and the unit is required to perform DLS sessions. Typically used where the
customer programs the control panel daily due to access control and still wants to receive alarms without buying extra hardware
(receiver) or software.
Note:
When a valid IP address has been programmed, Ethernet receiver 1 is enabled and will communicate events over the Ethernet
channel.
Ethernet receiver 1 and cellular receiver 1 may be configured to communicate to the same central station receiver. To configure the
device to operate using this common receiver mode functionality, program Ethernet receiver 1 and cellular receiver 1, IP address and
port number with identical values.
Note:
When operating in common receiver mode, Ethernet receiver 1 account code will be used for Ethernet and cellular.
[104] Ethernet Receiver 1 UDP Remote Port
Default (03061)
This Section determines the UDP remote port of Ethernet receiver 1. Valid range: 00000 - 65535.