Section 2: Installation
Power supply wiring
HSM2300/2204
The HSM2300/2204 power supply/high-current output module provides up to 1 A of additional current and can be used to add up to
four programmable outputs (HSM2204 only) to the alarm system.
The 4-wire Corbus connection provides communication between the module and alarm panel. Connect the RED, BLK, YEL and GRN
terminals to the Corbus terminals on the alarm controller. If O1 is not used, connect to Aux+ with a 1 K resistor. Board current draw is
35 mA. Battery standby capacity is at least 24 hours for fire applications. Recommended battery is DSC model BD7-12.
Note:
All terminals are Class 2 power limited, except battery leads.
Figure 2-27: HSM2300/2204 power supply wiring
RED
BLK
YEL
GRN
RED*
BLK*
Y
EL
GRN
CON1
BAT+ BAT-
Callout
Description
1
UL/ULC residential fire applications
2
Residential burglary applications
3
Tamper contact (normally closed)
4
To BLK
5
Corbus connection to control panel. RED, BLK 12 VDC at 20 mA.
6
AUX connection to expansion module. Refer to the Specifications Chart for maximum current draw.
7
Transformer (16.5 VAC / 40 VA. PTD1640U / PTD1640); Class 2
8
Power adapter (120 VAC / 60 Hz). EU, South Africa, Australia, NZ, and so on, 230 VAC, 50 Hz / 60 Hz.
9
Battery (12 v, 7 Ah. Maximum battery charge current is 360 mA)
10
Battery 1 (12 v, 7 Ah. Maximum battery charge current is 360 mA)
11
Battery 2 (same rating as battery 1)
12
Red (+) to BAT+ ; Blk (-) to BAT-
13
Supervised
14
Unsupervised