Section 6: Programming
With an audible alarm active, using the keyswitch when disarmed is the same as entering an access code at the keypad. Activating
this zone type during the first 30 seconds of a delayed fire alarm is the same as pressing a key at the keypad (the 90 second delay
starts). If left in the open state, the system does not arm until the zone is restored and tripped again.
068 – Momentary Keyswitch Disarm
Use with a keyswitch module. Activating and restoring this zone disarms the partition and silences alarms. Tampers or faults do not
disarm the zone.
Note:
Do not use as a global zone.
069 – Maintained Keyswitch Disarm
Used with a maintained keyswitch. Activating this zone disarms the partition.
Tampers or faults on this zone do not disarm the partition.
071 – Doorbell Zone
This zone type sounds a chime through keypads on the partition when activated. No alarms are generated. Various chime tones can
be programmed. Disabling door chime on the partition also disables the chime on this zone.
Note:
Do not use as a global zone.
072
–
Push to Set (Non CP-01 panels only)
Activating this zone starts an infinite exit delay when armed according to the methods described in the table below. To complete the
arming sequence, this zone must be activated and restored. Once done, the exit delay timer starts.
Note:
For UL installations, use a standalone keypad for each partition.
Arming method
Infinite exit delay
Arming mode
User code
Y
Away
Keyswitch
Y
Away
Away key
Y
Away
*0 arm
Y
Away
*9 arm
N
Stay
Stay key
N
Stay
Night key
N
Night
Remote access/SMS
-
Do not use
DLS arm
N
Away
No activity arming
N
Away
If you silence a fire alarm by entering a user code, and the zones that imitated the fire alarm remain open, a Bells Silenced message
displays. The system automatically clears the message when all the fire zones are restored on the system. When the Bells Silenced
message displays, a user can still view all standard base menu messages. The Bells Silenced message also overrides the automatic
display of the Alarm Memory feature for fire alarms.
Note:
Do not use exit delay termination with this zone type. Away arming with this zone bypassed prevents arming.
Note:
For Global Keypads, the Bells Silenced message will not be displayed. For UL installations, use the dedicated partition keypad
to view the Bell Silenced message.
[002] Zone attributes
Zone attributes are used to customize the operation of zones. When a zone type (section [001]) is programmed, the default zone
attribute is automatically assigned.
Note:
These attributes override default settings. Do not change fire zone attributes from their default settings.
[001]-[248] Select Zone
The attributes listed below can be enabled and disabled for each zone.
Table 6-5: Zone attributes
01 – Bell Audible
ON: An alarm activates the siren.
OFF: Silent alarm.
- 91 -