Section 6: Programming
Section 6: Programming
6.1 How to program
This section describes how to view alarm system programming options using the supported keypad types.
6.2 Programming methods
The alarm system can be programmed using the following methods:
Table 6-1: Programming Methods
Method
Description
Procedure
Template
programming
Use pre-defined templates to apply basic
programming and to set up DLS.
Press [899] on the
Enter Section
screen. See
for details.
DLS
programming
Download and apply programming using DLS 5.
For local DLS, use a micro USB cable or a Wi-Fi dongle and
laptop with DLS 5 software installed.
For remote DLS, use a telephone line, cellular network or the
Internet.
Installer
programming
Manually program all alarm system and device
options.
Press [*][8][installer code] while the system is disarmed.
Template programming
Use Template Programming to quickly program the minimum functions required for basic operation. Enter a 5-digit code that selects
predefined programming configurations:
Digit 1 – zone 1-8 definition options
Digit 2 – system EOL options
Digit 3 – alarm controller communications options
Digit 4 – alarm controller call directions
Digit 5 – DLS connection options
Perform template programming after completing the hardware installation. Ensure you have the information listed below available.
Record this information in the programming worksheets for future reference:
l
Monitoring station telephone number - provided by the alarm monitoring service.
l
Monitoring station account code - provided by the alarm monitoring service.
l
Downloading access code.
l
Entry delay - installer defined.
l
Exit delay - installer defined.
l
Installer code - programmable, unique 4-digit code. The default value is
[5555]
.
To perform template programming:
1. Enter
[*][8][installer code][899]
. If this section has been entered accidentally, press
[#]
to exit and the system programming will
not be changed.
2. Enter a 5-digit value representing the desired programming options on the
Enter Data
screen. Reference the
for programming information to determine what values are required for the installation.
Once the 5-digit number has been entered, the installer cannot exit until all sections are completed. Enter new data and/or
press the [#] key to accept the displayed data and proceed to the next section. Changing a single digit, then pressing the [#]
key advances to the next section but does not save the changed data.
3. After entering a 5-digit template programming value, the first telephone number is displayed. Enter the monitoring station
telephone number after the “D.” Press
[#]
to complete the entry.
4. After programming the first telephone number, enter a system account code.
l
The system account code can be any 4 or 6-digit combination of numbers (0-9) and letters (A-F).
l
To enter letters
A
through
F
, press
[*]
then the numbers
1
through
6
for the letter A through F respectively. Press
[*]
again to
revert back to decimal entry. E.g., to enter “1234FF” press [1234*66].
When the system account code programming is completed, enter a partition 1 account code using the same method as the
system account code.