Refer to "Regulatory approvals" on page 304.
for detailed Aux. loading and battery charging information.
Complete the following chart to find (A), complete the following formula to find the battery capacity (B) and refer to the
HS3032/3128/HS3248 alarm controller battery selection chart above.
(Total standby current ________ mA
(A)
x Standby time ________ hours) + (Alarm current x Alarm time ________ hours \ 1000) = __
_____ Ah
(B)
Aux loading and battery selection
HS3032/ HS3128/
HS3248
PCB current draw
120 mA
Alarm current 700
mA
UL Resi Burg
ULC Resi
Burg
UL Com Burg
UL Resi Fire UL
Home Health
Care ULC Resi
Fire ULC Com
Burg
UL Resi Fire
with wired CO
Detectors
UL985 6th Ed
ULC COM Fire
Monitoring
EN50131
Grade 2
EN50131
Grade 3
Standby Time and
Alarm Time
4 h + 4 min
4 h + 5 min
4 h + 15 min
24 h + 4 min
24 h + 5 min
24 h + 4 min
24 h + 4 min +
12 h CO alarm
24 h + 30 min
12 h
30 h (AC fail
transmission
required)
60 h
Enclosure
HSC3010C
HSC3030CAR
HSC3010C
HSC3010C
HSC3010CR
HSC3020C
HSC3020C
Power Supply
Adapter
HS65WPSNA HS65WPSNA
HS65WPSNA
HS65WPSNAS
(ULC CB
Security Level 4)
(Require high
voltage barrier
kit)
HS65WPSNA HS65WPSNAS
HS65WPS
HS65WPS
Battery capacity
/max loading
4 Ah/700 mA
7 Ah/1200
mA
14 Ah/2000
mA
17 Ah/2000
mA
4 Ah/700 mA
7 Ah/1200 mA
14 Ah/2000
mA
17 Ah/2000
mA
7 Ah/250 mA
14 Ah/500 mA
17 Ah/600 mA
14 Ah/330 mA
17 Ah/400 mA
14 Ah/500 mA
17 Ah/600 mA
17 Ah/
1200 mA
17 Ah/500
mA
17 Ah/250
mA
Recharging current
setting
Low (400
mA) for
4 Ah/High
(700 mA)
Low (400 mA)
for 4Ah/High
(700 mA)
High (700 mA)
High (700 mA) High (700 mA)
Low
(400 mA)
High
(700mA)
Note:
For NFA2P 2 shield installations, use 18 Ah batteries and 450 mA load for 36-hour standby. For NFA2P 3 shield installations,
use 18 Ah batteries and the same loadings as for EN50131 Grade 3 in the table above.
Connecting AC power
The alarm controller requires an 18 VDC switched mode power supply. For information on connecting AC power, see
- 53 -