Goodrive20-UL Series VFD
Function parameters
-85-
Function
code
Name
Description
Default Modify
P09.18
Integral
time at low
frequency
(Ti)
0.00
–10.00 s
0.10 s
○
P09.19
Differential
time at low
frequency
(Td)
0.00
–10.00 s
0.00 s
○
P09.20
Low-point
frequency
for
switching
PI
parameters
0.00 Hz
–P09.21
When the ramp frequency is less than or equal
to P09.20, the present PID parameters range
from P09.17 to P09.19. When the ramp
frequency is greater than or equal to P09.21,
the present PI parameters range from P09.04
to P09.06. The intermediate frequency band is
the linear interpolation between high and
low-point frequency.
5.00 Hz
○
P09.21
High-point
frequency
for
switching
PI
parameters
P09.20
–P00.03
10.00 Hz
○
P10 group Simple PLC and multi-step speed control
Function
code
Name
Description
Default Modify
P10.00
Simple
PLC mode
0: Stop after running once; the VFD stops
automatically after running for one cycle, and it
can be started only after receiving running
command.
1: Keep running in the final value after running
once. The VFD keeps the running frequency
and direction of the last section after a single
cycle.
2: Cyclic running; the VFD enters the next cycle
after completing one cycle until receiving stop
command and stops.
0
○
Содержание GD20-0R4G-2-UL
Страница 1: ......
Страница 160: ...201905 V1 6 6 6 0 0 1 0 0 4 3 0 66001 00392...