Goodrive20-UL Series VFD
Function parameters
-34-
Function
code
Name
Description
Default Modify
when high control accuracy is needed.
2: Static autotuning 1 (autotune totally); It is
suitable in the cases when the motor can not
de-couple from the load. The antotuning for the
motor parameter will impact the control
accuracy.
3:
Static
autotuning
2
(autotune
part
parameters); when the current motor is motor 1,
autotune P02.06, P02.07, P02.08
P00.16
AVR
function
selection
0: Invalid
1: Valid during the whole procedure
The auto-adjusting function of the VFD can
cancel the impact on the output voltage of the
VFD because of the bus voltage fluctuation.
1
○
P00.18
Function
restore
parameter
0
–6
0: No operation
1: Restore the default value (excluding the
motor parameters)
2: Clear fault records
3: Function code locking (lock all function
codes)
4: Reserved
5: Restore the default value (factory test mode)
6: Restore the default value (including the motor
parameters)
Note:
After the selected operation is performed, the
function code is automatically restored to 0.
Restoring default values may delete the user
password. Exercise caution when using this
function.
Restoring default values (factory test mode)
will restore the parameters to the
corresponding standard version.
Non-professionals shall exercise caution
when using this function.
0
◎